Digital inputs setup menu – SATEC PM296 User Manual
Page 32
Chapter 4 Setup Menus
24
Code Parameter Options Description
dAtA
Data format
7E
7 bits, even parity
8n
∗
8 bits, no parity
8E
8 bits, even parity
H.Sh
Incoming flow
nonE
∗
No handshaking
control (handshaking) SOFt
Software handshaking
(XON/XOFF protocol)
Hard
Hardware handshaking (CTS
protocol)
Ctrl
Outgoing flow control nonE
∗
RTS signal not used
(RTS/DTR)
dtr
RTS permanently asserted
(DTR mode)
rtS
RTS asserted during the
transmission
Prn.P
Printout period
1
∗, 2, 5, 10, 15,
Time interval between
20, 30, 60
min
successive printouts
COM2
Code Parameter Options Description
Prt.2
Communications
protocol
ASCII
∗
rtu
dnP3
ASCII protocol
Modbus RTU protocol
DNP3.0 protocol
rS
Interface standard
422
RS-422 interface
485
∗
RS-485 interface
Addr
Address
0
∗-99 ASCII
1
∗-247 Modbus
Powermeter address
bAud
Baud rate
110
110 baud
300
300 baud
600
600 baud
1200
1200 baud
2400
2400 baud
4800
4800 baud
9600
∗
9600 baud
19.20
19,200 baud
38.40
38,400 baud
dAtA
Data format
7E
7 bits, even parity
8n
∗
8 bits, no parity
8E
8 bits, even parity
CPtb
ASCII compatibility
mode
diS
∗
, En
Disables/enables ASCII
compatibility mode. For more
information, see ASCII
Communications Protocol
Reference Guide