Chapter 4 Setup Menus
23
4.2 Communications Port Setup Menus
These menus allow you to access the communications port options that the
PM296/RPM096
uses to communicate with a master computer or a printer. Table
4-2 lists the communications options, their code names and applicable choices.
From the main menu, select the menu for the port you want to configure. Activate
the middle window to scroll through the list of available options, and then activate
the lower window to set the option value.
To select and view a setup option:
Press to activate the middle window.
Use the up/down arrow keys to scroll to the desired option. The option setting will
appear in the lower window.
To change the selected option:
Press to activate the lower window.
Press the up/down arrow keys to scroll to the desired value.
Press to store the selected value or press to quit the setup menu.
NOTE:
An optional analog expander can be connected to Communications Port #2.
Table 4-2 Communications Options
(
∗ default setting
)
COM1
Code Parameter Options Description
Prt.1
Communications
protocol
ASCII
∗
rtu
dnP3
Prnt
ASCII protocol
Modbus RTU protocol
DNP3.0 protocol
Printer mode
rS
Interface standard
232
RS-232 interface
485
∗
RS-485 interface
Addr
Address
0
∗-99 ASCII
1
∗-247 Modbus
0*-255 DNP3.0
Powermeter address
bAud
Baud rate
110
110 baud
300
300 baud
600
600 baud
1200
1200 baud
2400
2400 baud
4800
4800 baud
9600
∗
9600 baud
19.20
19,200 baud
38.40
38,400 baud
Prt.1
ASCII
Prot
ESC
ENTER
SELECT
SELECT
SELECT
CHG
ENTER
Prt.1
ENTER
SELECT
CHG
ENTER
Prt.2
ENTER