Chapter 4 Setup Menus

29

Code Parameter Unit Scale

rt P

Total kW

kW/MW

-Pmax to Pmax

rt q

Total kvar

kvar/Mvar

-Pmax to Pmax

rt S

Total kVA

kVA/MVA

0 to Pmax

rt PF

Total PF

-0.000 to 0.000

rt PF.LG

Total PF lag

0 to 1.000

rt PF.Ld

Total PF lead

0 to 1.000

rt Au.C

Auxiliary current

A/mA

0 to Imax aux

rt nEU.C

Neutral current

A

0 to Imax

rt Fr

Frequency

Hz

0 to 100.00

rt U.dC

DC Voltage

V

0 to 9999.00

Average Measurements

Ar U 1

Voltage L1/L12

V/kV

0 to Vmax

Ar U 2

Voltage L2/L23

V/kV

0 to Vmax

Ar U 3

Voltage L3/L31

V/kV

0 to Vmax

Ar U.AG

3-phase average voltage

V/kV

0 to Vmax

Ar U.L12

Voltage L12

V/kV

0 to Vmax

Ar U.L23

Voltage L23

V/kV

0 to Vmax

Ar U.L31

Voltage L31

V/kV

0 to Vmax

Ar U.L.AG

3-phase average L-L voltage

V/kV

0 to Vmax

Ar C1

Current L1

A

0 to Imax

Ar C2

Current L2

A

0 to Imax

Ar C3

Current L3

A

0 to Imax

Ar C.AG

3-phase average current

A

0 to Imax

Ar P

Total kW

kW/MW

-Pmax to Pmax

Ar q

Total kvar

kvar/Mvar

-Pmax to Pmax

Ar S

Total kVA

kVA/MVA

0 to Pmax

Ar PF

Total PF

-0.000 to 0.000

Ar PF.LG

Total PF lag

0 to 1.000

Ar PF.Ld

Total PF lead

0 to 1.000

Ar Au.C

Auxiliary current

A/mA

0 to Imax aux

Ar neU.C

Neutral current

A

0 to Imax

Ar Fr

Frequency

Hz

0 to 100.00

Present Demands

Acd.P.i

Accumulated kW import demand

kW/MW

0 to Pmax

Acd.P.E

Accumulated kW export demand

kW/MW

0 to Pmax

Acd.q.i

Accumulated kvar import demand

kvar/Mvar

0 to Pmax

Acd.q.E

Accumulated kvar export demand

kvar/Mvar

0 to Pmax

Acd.S

Accumulated kVA demand

kVA/MVA

0 to Pmax

Imax

(100% over-range) = 2

× CT primary current [A]

Imax

aux (100% over-range) = 2

× Auxiliary CT primary current [A]

Direct wiring (PT Ratio = 1):

Vmax

(690 V input option) = 828.0 V

Vmax

(120 V input option) = 144.0 V

Pmax

= (Imax

× Vmax × 3) [kW x 0.001] @ wiring modes 4Ln3, 3Ln3

Pmax

= (Imax

× Vmax × 2) [kW x 0.001] @ wiring modes 4LL3, 3OP2, 3dir2, 3OP3, 3LL3

NOTE: Pmax

is rounded to nearest whole kW units.

If Pmax is more than 9999.000 kW, it is truncated to 9999.000 kW