Appendix: Technical Specifications
69
Accuracy, %
Range
Display resolution (%Rdg)
Parameter
Full scale
Rdg FS Conditions
@ range
Neutral (unbalanced)
current
CT PRIMARY CURRENT
0.5 2% to 120% FS
0 to 9999 A
0.01 A @ 0.01A to 99.99 A
≤
0.1% @ 100.0 A to 9999 A
Starting current 0.5% FS
Ampere demand
same as for current
KW demand (block & sliding) same as for kW
KVA demand (block & sliding ) same as for kVA
Total Harmonic
Distortion
THD U (I), % U1 (I1)
999.9 1.5
0.2
≥
0.1% FS,
U (I)
≥
10% FSU
(FSI)
0 to 999.9
0.1
Total Demand
Distortion TDD (I), %
100
1.5
≥
1% FSI,
I
≥
10% FSI
0 to 100
0.1
Active energy
Import & Export
same as for power
0 to 99,999 MWh 1 kWh @ 1 to 99,999 kWh
10 kWh @ 100 to 999.99 MWh
100 kWh @ 1,000 to 9,999.9 MWh
1MWh @ 10,000 to 99,999 MWh
Reactive energy
Import & Export
same as for power
0 to 99,999 Mvarh 1 kvarh @ 1 to 99,999 kvarh
10 kvarh @ 100 to 999.99 Mvarh
100 kvarh @ 1,000 to 9,999.9 Mvarh
1Mvarh @ 10,000 to 99,999 Mvarh
Apparent energy
same as for power
0 to 99,999 MVAh 1 kVAh @ 1 to 99,999 kVAh
10 kVAh @ 100 to 999.99 MVAh
100 kVAh @ 1,000 to 9,999.9 MVAh
1MVAh @ 10,000 to 99,999 MVAh
PT = external potential transformer ratio
CT, CT Primary Current = primary current rating of external current transformer
FSU = voltage full scale
FSI = current full scale
U1 = voltage fundamental
I1 = current fundamental
@ 10% to 120% of voltage FS and 2% to 120% of current FS Higher resolution is achievable via communications
Where the current is
>
10% FS, the energy accuracy is better than 1.5% Rdg.
Additional Notes
1. Accuracy is expressed as
±
(percentage of reading + percentage of full scale)
±
1 digit. This does not include inaccuracies introduced
by the user's potential and current transformers.
2. Specifications assume: voltage and current wave forms with THD
≤
5% for kvar, kVA and PF; reference operating temperature: 20 - 26
°
C.
3. Ordinary measurement error is considerably less than the specified accuracy which indicates maximum error.