Chapter 4 Setup Menus

35

Code

Parameter Options

Description

Ph.En

Phase energy
measurements

diS

*

, En

Enables/disables measurements of energies
per phase

Power calculation mode (P.cAL):

Mode 1: Reactive power calculation (rEAc)

Active power P and reactive power Q are measured directly and apparent power
S =

P

2

+ Q

2

Mode 2: Non-active power calculation (nAct)

Active power is measured directly, apparent power S = V

×

I (where V, I - rms

voltage and currents) and non-active power N =

S

2

-

P

2

Mode 1 is recommended for electrical networks with low harmonic distortion (voltage
THD

<

5%, current THD

<

10%); Mode 2 is recommended for all other cases.

Energy roll value example: If roll value = 10.E4, the energy counter contains 4 digits,

i.e., energy is displayed up to 9.999 MWh (Mvarh, MVAh) with resolution 0.001 MWh.

Rollover
Value

Maximum Energy

kWh (kvarh, kVAh)

Maximum Display Reading
MWh (Mvarh, MVAh)

Display Resolution
MWh (Mvarh, MVAh)

10.E4

9,999

9.999

0.001

10.E5 99,999

99.999

0.001

10.E6 999,999

999.99

0.01

10.E7 9,999,999

9,999.9 0.1

10.E8

99,999,999

99,999

1

The roll value may be changed in accordance with the average load of the power line.
For example, if average power is 400 kW and the counter must be reset every 3 months
(2160 hours), then energy during this period equals 864000 kWh (6 digits) and the roll
value = 10.E6.