SATEC C192PF8-RPR User Manual
Page 40

Chapter 4 Setup Menus
35
Code
Parameter Options
Description
Ph.En
Phase energy
measurements
diS
*
, En
Enables/disables measurements of energies
per phase
Power calculation mode (P.cAL):
Mode 1: Reactive power calculation (rEAc)
Active power P and reactive power Q are measured directly and apparent power
S =
√
P
2
+ Q
2
Mode 2: Non-active power calculation (nAct)
Active power is measured directly, apparent power S = V
×
I (where V, I - rms
voltage and currents) and non-active power N =
√
S
2
-
P
2
Mode 1 is recommended for electrical networks with low harmonic distortion (voltage
THD
<
5%, current THD
<
10%); Mode 2 is recommended for all other cases.
Energy roll value example: If roll value = 10.E4, the energy counter contains 4 digits,
i.e., energy is displayed up to 9.999 MWh (Mvarh, MVAh) with resolution 0.001 MWh.
Rollover
Value
Maximum Energy
kWh (kvarh, kVAh)
Maximum Display Reading
MWh (Mvarh, MVAh)
Display Resolution
MWh (Mvarh, MVAh)
10.E4
9,999
9.999
0.001
10.E5 99,999
99.999
0.001
10.E6 999,999
999.99
0.01
10.E7 9,999,999
9,999.9 0.1
10.E8
99,999,999
99,999
1
The roll value may be changed in accordance with the average load of the power line.
For example, if average power is 400 kW and the counter must be reset every 3 months
(2160 hours), then energy during this period equals 864000 kWh (6 digits) and the roll
value = 10.E6.