Appendix: Technical Specifications
68
Measurement Specifications
Accuracy, %
Range
Display resolution (%Rdg)
Parameter
Full scale
Rdg FS Conditions
@ range
Voltage
120V
×
PT
@ 120V
400V
×
PT
@ 690V
208V
×
PT
@ 120V
690V
×
PT
@ 690V
0.25 10% to 120% FS 0 to 999,000 V
Direct wiring (PT=1):
0.1 V @ 0.1V to 999.9 V
Wiring via PTs (PT>1):
0.001 kV @ 0.001kV to 9.999 kV
≤
0.1% @ 10.00 kV to 999.0 kV
Starting voltage 1.5% FS
Line current
CT PRIMARY CURRENT
0.25 2% to 120% FS
0 to 9999 A
0.01 A @ 0.01A to 99.99 A
≤
0.1% @ 100.0 A to 9999 A
Starting current 0.5% FS
Active power
0.36
×
PT
×
CT @ 120V input
1.2
×
PT
×
CT @ 690V input
0.5
|PF|
≥
0.5
-2,000,000 to
+2,000,000 kW
Direct wiring (PT=1):
0.001 kW @ 0.001kW to 9.999 kW
Wiring via PTs (PT>1):
0.001 MW @ 0.001MW to 9.999 MW
≤
0.1% @ 10.00 MW to 2000 MW
Reactive power
0.36
×
PT
×
CT @ 120V input
1.2
×
PT
×
CT @ 690V input
0.5
|PF|
≤
0.9
-2,000,000 to
+2,000,000 kvar
Direct wiring (PT=1):
0.001 kvar @ 0.001kvar to 9.999 kvar
Wiring via PTs (PT>1):
0.001 Mvar @ 0.001Mvar to 9.999 Mvar
≤
0.1% @ 10.00 Mvar to 2000 Mvar
Apparent power
0.36
×
PT
×
CT @ 120V input
1.2
×
PT
×
CT @ 690V input
0.5
|PF|
≥
0.5
0 to
2,000,000 kVA
Direct wiring (PT=1):
0.001 kVA @ 0.001kVA to 9.999 kVA
Wiring via PTs (PT>1):
0.001 MVA @ 0.001MVA to 9.999 MVA
≤
0.1% @ 10.00 MVA to 2000 MVA
Power factor
1
1
|PF|
≥
0.5,
I
≥
10% FSI
-0.999 to +1.000 0.001
Frequency
0.02
45.00 to 65.00 Hz 0.01 Hz
or
or
For Ln reading
and for
3
OP2/3OP3
wiring modes
For LL reading
except
3OP2/3OP3
wiring modes