Chapter 2 Installation

15

2.2.7 Status Input

One status input is provided for status monitoring or external synchronization
input for power demand period.

Figure 2-12 Status Input Connection

2.2.8 Analog Output

The C192PF8-RPR provides one optically isolated analog output with current
output options of 0-20 mA and 4-20 mA (current loop load of up to 500 Ohm). The
analog output must be used with a 24 V DC external power supply.

Figure 2-13 Analog Output Connection