66 • Replacing the AC Fuses

Beacon 410 Gas Monitor Operator’s Manual

Replacing the AC Fuses

The Beacon 410 has two user serviceable AC fuses.

NOTE:

To replace other components of the Beacon 410, contact RKI Instruments, Inc.,
for further information.

1.

Turn off or unplug all incoming power to the Beacon 410.

2.

Open the Beacon 410 housing door, then place the power switch in the OFF position.

3.

The fuses are located to the left of the AC in terminal strip. Use a flat-blade
screwdriver to rotate the applicable fuse holder 1/4 turn counterclockwise. The fuse
holder releases from the socket.

4.

Remove the fuse holder from the socket, then remove the fuse from the fuse holder.

CAUTION: Verify that the replacement fuses are the same type and rating as the fuses

you are replacing. The Beacon 410’s fuses are fast blow fuses rated for
6A, 250 V

5.

Install the replacement fuse in the fuse holder, then place the fuse holder in the
socket.

6.

Push the fuse holder into the socket, then turn the holder 1/4 turn clockwise to secure
it in the socket.

7.

Plug in or turn on all incoming power to the Beacon 410.

8.

Place the Beacon 410’s power switch in the ON position, then verify that the PILOT
light is on.

9.

Close and secure the housing door.

Parts List

Table 22 lists the part numbers and descriptions for replacement parts and accessories
offered for the Beacon 410 Gas Monitor.

Table 22: Parts List, Beacon 410 Gas Monitor

Part No.

Description

18-0107RK

Conduit Hub (3/4 in.)

43-0440RK

Reset Switch

43-4170RK

Fast Blow Fuse, 6A, 250 V

51-0096RK

Strobe/horn, 10-33 VDC, NEMA 4X

52-1016RK

Buzzer

71-0131RK

Beacon 410 Gas Monitor Operator’s Manual (this document)