RKI Instruments Beacon 410 User Manual
Page 48

44 • Selecting the Detector Head Input Type and Gas Setup
Beacon 410 Gas Monitor Operator’s Manual
10. If you want to save the setup, press and release the UP/YES button. The display will
indicate that the settings have been saved before asking if you want to setup more
channels.
NOTE:
If you defined a custom setup by selecting the CUSTOM choice in the
PreDefined Gas Setup screen, you will be required to review the channel
parameters from the Configuration Menu. See “Viewing and Changing Channel
Parameters” on page 35 for a description of the channel parameters.
If you do not want to save the setup, press and release the DOWN/NO button. You will
return to the Select Channel(s) screen. Follow the instructions from step 4 above.
11. If you want to setup more channels, press and release the UP/YES button. You will
return to the Select Channel(s) screen. Follow the instructions from step 4 above.
If you do not want to setup more channels, press and release the DOWN/NO button
and the Beacon 410 will exit the Input Setup Menu and begin its warm-up sequence.