MCH CONTROL WIRING DIAGRAMS
The following wiring diagrams apply to standard MCH drives. Refer to Appendix A for
control wiring for the Bypass option, or Appendix B for control wiring for the Option Box.
15.1
MCH TERMINAL STRIP
Shown below is the terminal strip on the main control board, along with a brief description
of the function of each terminal.
RUN / ST
OP
CIR
CUIT C
OMMON
0-10
VDC SPEED REFERENCE INPUT
10
VDC SUPPL
Y FOR SPEED PO
T
0-10 OR 2-10
VDC OUTPUT
: FREQUENC
Y
0-10 OR 2-10
VDC OUTPUT
: L
O
AD
CIR
CUIT C
OMMON
AUT
O MODE SELEC
T
TB
-13A FUNC
TION SELEC
T
TB
-13B FUNC
TION SELEC
T
TB
-13C FUNC
TION SELEC
T
TB
-13D FUNC
TION SELEC
T
OPEN-
COLLEC
TOR OUTPUT
OPEN-
COLLEC
TOR OUTPUT
RS
-485 SERIAL
COMMUNIC
ATIONS
CIR
CUIT C
OMMON
4-20 mA SPEED REFERENCE INPUT
1 2 5A 5B 6 10A
12A
RXA TXB
10B 2
13A 13B 13C 13D 14 15 2
16 17 18
FORM C
RELAY
The TB-2 terminals are internally tied together
NOTE:
The function of terminals TB-10A, TB-10B, TB-13A, TB-13B, TB-13C, TB-
13D, TB-14, TB-15, TB-16 and TB-18 are dependent on the programming
of certain parameters. In most cases, the name of the parameter matches
the number of the terminal, allowing quick and easy programming of the
terminals to suit the application. The exception is TB-16 and TB-18, which
are governed by Parameter 54 - RELAY.
A complete description of operating the drive in the AUTO mode can be found in Section
14.2. The following diagrams provide a quick reference to wire the drive for the most
common configurations.