11 mch power wiring diagram – Lenze MCH Series User Manual
Page 28

24
13435744_EDBMH01_v13
11
MCH POWER WIRING DIAGRAM
This diagram applies to standard MCH drives. Refer to Appendix A for Bypass power
wiring or Appendix B for Option Box power wiring.
T1 T2 T3
L1 L2 L3
FUSED INPUT
VOLTAGE
GND
GND
GND
DISCONNECT
MEANS
(REQUIRED)
THREE PHASE
AC MOTOR
WARNING!
Do NOT connect incoming AC power to output terminals T1, T2 or
T3. Severe damage to the drive will result.
INSTALL, WIRE AND GROUND IN ACCORDANCE WITH ALL APPLICABLE CODES.
NOTES:
1.
Wire the motor for the proper voltage per the output rating of the drive. Motor wires
MUST be run in a separate steel conduit away from control wiring and incoming
AC power wiring.
2.
Do not install contactors between the drive and the motor without consulting Lenze
AC Tech for more information. Failure to do so may result in drive damage.
3.
Remove any existing, and do not install, power factor correction capacitors
between the drive and the motor. Failure to do so will result in drive damage.
4.
Use only UL and CSA listed and approved wire.
5.
Minimum wire voltage ratings: 300 V for 200 and 240 Vac systems and 600 V for
400, 480, and 590 Vac systems.
6.
Wire gauge must be based on a minimum of 125% of the rated output current of
the drive, and a minimum 75°C insulation rating. Use copper wire only.
7.
Wire and ground in accordance with NEC or CEC, and all applicable local codes.