15

4 Electrical connection

4.1

Safety information

The electrical connection must only be carried out by qualified personnel.

When mounting, connecting, and operating the transmitter, ensure that no electrostatic
charging can take place.

The transmitter is not suitable for installation and application areas with an explosion haz-
ard.

Never expose the transmitter to magnetic or electrical fields (e.g. caused by transformers,
walkie-talkies, or electrostatic discharge).

An electrical connection that deviates from the connection diagram can destroy the trans-
mitter.

The transmitter is suitable for use in SELV or PELV current circuits according to protection
rating 3. The case implements basic insulation of up to 50 V towards neighboring devices.

4.2

Terminal assignment and dimensions (mm) of
dTRANS T05 B

5
Ш

44
Ш

7

Ш

33

21

Connection for

Terminal assignment

Voltage supply

Type 707050

R

B

= (V

b

- 11 V)/22 mA

DC 11 to 35 V

Current output

R

B

= Load resistance

4 to 20 mA

V

b

= Voltage supply

2

1

+