Prepare for Installation

Where to Install the Rough-in

The DRd Semi-Recessed installation kit is designed to allow installation of a DRd rack into a wall cavity,
between 2”x4” or 2”x6” framed wall studs. The installation depth of the rough-in enclosure determines
how much the DRd rack enclosure will extend from the finished surface.

DRd Rack Enclosure Specification and Installation

Reference the DRd Rack Enclosure Installation Manual for rack installation details, including all
mechanical, electrical and control wire requirements.

Rough-in Dimensions

C A U T I O N :

Unison DRd rack enclosures require at least 17” (432mm) of front clearance and 6”

(152mm) of clearance to the left of the DRd rack door hinge from walls or other

equipment to allow for installation and removal of modules after installation.

If you do not allow this clearance, energization, operation and maintenance of your

DRd rack enclosure will be significantly difficult.

Kit Type

Height

Width

Depth

Semi-

recessed kit

Product

Weight

inches

mm

inches

mm

inches

mm

lbs

kgs

DRd6 Semi-Recessed kit

32.25

819

20

448

4

102

15

6.8

DRd12 Semi-Recessed kit

41.5

1,054

20

448

4

102

19

9

DRd6 kit

32.25”

(819mm)

DRd12 kit

41.5”

(1,054mm)

Both kits are

20” (559mm)

Both kits are

4” (102mm)

The dimensions in the table below are provided for the
rough-in only and do not include the cover or DRd rack
measurements for depth.

It is recommended that you install the rough-in at least
36” (915mm) off the floor surface to ensure clear view
of the user interface.

The wall framing and blocking must be strong enough
to hold the semi-recessed kit and DRd rack fully
populated with modules, conduit and wire
(approximately 140 lbs / 63.5kg).

The weights noted below are specific to the rough-in
only and do not include conduit, hardware, cable, rack
and module weights.

For accurate, application-specific, DRd rack enclosure
and module weights, reference the Unison DRd Rack
Enclosure Installation Manual
.