SECTION 6 - JLG CONTROL SYSTEM
3121181
– JLG Lift –
6-83
8/4
Flash code 8/4 indicates problems with the envelope system.
Only occur on machines with envelope control.
10
BOOM ANGLE SENSOR DISAGREEMENT The boom angle sensors are reporting angles that differ too greatly.
An EMS cycle is required.
BOOM LENGTH SWITCH FAILED
The boom length switch inputs are reporting the same state. An EMS
cycle is required.
BOOM LENGTH SWITCH/SENSOR DIS-
AGREEMENT
The boom length switch and sensor differ in their reports of
extended or retracted. An EMS cycle is required.
BOOM LENGTH SENSOR NOT DETECT-
ING LENGTH CHANGE
The boom length sensor has not detected a change in length while
the user is commanding telescope. An EMS cycle is required.
BOOM LENGTH SENSOR OUT OF RANGE
HIGH
Indicates that the voltage for the boom length sensor is above the
expected range.
BOOM LENGTH SENSOR OUT OF RANGE
LOW
Indicates that the voltage for the boom length sensor is below the
expected range.
BOOM LENGTH SENSOR VALUE OUT OF
RANGE HIGH
Indicates the length reported for the boom length sensor is above
the expected range. An EMS cycle is required.
BOOM LENGTH SENSOR VALUE OUT OF
RANGE LOW
Indicates the length reported for the boom length sensor is below
the expected range. An EMS cycle is required.
BOOM ANGLE SENSOR #1 COMMUNI-
CATIONS FAULT
Boom angle sensor #1 lost communications with the BLAM. An EMS
cycle is required.
BOOM ANGLE SENSOR #2 COMMUNI-
CATIONS FAULT
Boom angle sensor #2 lost communications with the BLAM. An EMS
cycle is required.
ANGLE SENSOR #1 INVALID ANGLE
An EMS cycle is required.
ANGLE SENSOR #2 INVALID ANGLE
An EMS cycle is required.
WRONG TELE RESPONSE
The boom telescope is contrary to the user command
WRONG LIFT RESPONSE
The boom lift is contrary to the user command
TOWER ANGLE SENSOR DISAGREE-
MENT
The tower angle sensors are reporting angles that differ too greatly.
An EMS cycle is required.
TOWER LENGTH SENSOR DISAGREE-
MENT
The tower length sensors are reporting angles that differ too greatly.
An EMS cycle is required.
MAIN ANGLE SENSOR DISAGREEMENT
The main boom angle sensors are reporting angles that differ too
greatly. An EMS cycle is required.
BOOM LENGTH SENSOR #1 OUT OF
RANGE HIGH
Reported from the BLAM, indicates tower length sensor one value is
out of range high.
BOOM LENGTH SENSOR #1 OUT OF
RANGE LOW
Reported from the BLAM, indicates tower length sensor one value is
out of range low.
BOOM LENGTH SENSOR #2 OUT OF
RANGE HIGH
Reported from the BLAM, indicates tower length sensor two value is
out of range high.
BOOM LENGTH SENSOR #2 OUT OF
RANGE LOW
Reported from the BLAM, indicates tower length sensor two value is
out of range low.
TWR LENGTH SENSOR NOT DETECTING
LENGTH CHANGE
Tower tele is being commanded and the length sensors are not
changing value.
TWR LENGTH MOVEMENT WITHOUT
CMD
Tower length is changing without a tower tele command
TWR LENGTH SENSOR ONE VALUE OUT
OF RANGE HIGH
This fault is reported by the Ground module when the length sensor
value is outside the constant data limit
Table 6-9. Help Fault Codes, Displayed Faults, and Descriptions
Fault Flash
Code
Analyzer Display
Description
Priority