Adding Wired Sensors

Adding Wired Sensors

Adding a Wired Sensor

The procedure shown below adds a wired blue temperature sensor, but is applicable to other wired sensors as

well.

The Hysteresis setting helps prevent alarms from being set and reset continually if the environment is at or near

the alarm set point by providing an acceptable variance. For example, if

HYSTERESIS is set at 1 and the sensor High

Alarm Limit is set at +158, the sensor reading must decrease to +157 (+157 minus 1) in order for the temperature

alarm to reset to a no-alarm condition.

When setting numeric values, use the arrow keys to change the value. Use the PREV and NEXT soft keys to move

the cursor to the next or previous digit. Press the ENTER key to enter the value.

This is the start screen for the next
sensor to be added, if any.

F3

NOTE: Select the sensor number that
matches the input number used by the
sensor, or an alarm may result.

Example values are shown. Set all limit
values as appropriate for your system.