Relay operation – Winland Electronics EA800-ip User Manual

Page 21

background image

General Information

D-011-0152

21

Relay Operation

This section describes the operation of the console's relays. The relays must be programmed correctly so that their

outputs provide the desired signaling to the alarm panel.

Table 12

Relay Configuration Settings

Relay Setting

Description

No Alarm

Relay State:

De-Energized (default)

No Alarm: Power is removed from the relay coil as shown at

right.

Alarm: Power is applied to the relay coil as shown at right.

No Alarm

Relay State: Energized

No Alarm: Power is applied to the relay coil as shown at

right.

Alarm: Power is removed from the relay coil as shown at

right. This provides for a default alarm if the EA800 loses

power in addition to the sensors' alarms.

Active Condition:

Alarm Only

Sets the alarm to be active when an alarm condition exists.

Active Condition:

Alarm or Warning (default)

Sets the alarm to be active when an alarm condition exists or a warning is active.

Active Condition:

Warning Only (Aux only)

Sets the Aux relay to be active only when a warning occurs. This can be useful in

notifying for a low-battery condition.