Relay operation – Winland Electronics EA800-ip User Manual
Page 21

General Information
D-011-0152
21
Relay Operation
This section describes the operation of the console's relays. The relays must be programmed correctly so that their
outputs provide the desired signaling to the alarm panel.
Table 12
Relay Configuration Settings
Relay Setting
Description
No Alarm
Relay State:
De-Energized (default)
No Alarm: Power is removed from the relay coil as shown at
right.
Alarm: Power is applied to the relay coil as shown at right.
No Alarm
Relay State: Energized
No Alarm: Power is applied to the relay coil as shown at
right.
Alarm: Power is removed from the relay coil as shown at
right. This provides for a default alarm if the EA800 loses
power in addition to the sensors' alarms.
Active Condition:
Alarm Only
Sets the alarm to be active when an alarm condition exists.
Active Condition:
Alarm or Warning (default)
Sets the alarm to be active when an alarm condition exists or a warning is active.
Active Condition:
Warning Only (Aux only)
Sets the Aux relay to be active only when a warning occurs. This can be useful in
notifying for a low-battery condition.