beautypg.com

Sensors, Temperature sensors – Winland Electronics EA800-ip User Manual

Page 15

background image

General Information

D-011-0152

15

Sensors

A variety of sensors may be used with the EA800 console to provide environmental status and information. These

include the following:

Wired Sensors: Outputs 1 through 4 are for use with sensors wired to the console. Wired sensors can be any
of the following types:

Low temperature - blue thermistor probe

High temperature - red thermistor probe

Ultra low temperature - white thermistor probe

HA-III+ humidity sensor

WaterBug

®

sensor (supervised only)

Normally Open (N.O.) dry contact

Normally Closed (N.C.) dry contact

4-20 mA

Wireless Sensors: Outputs 5 through 8 are for use with wireless sensors. These sensors transmit to the EA800
console through RF links. Each wireless sensor is hard-coded with an address the console uses to identify the
sensors installed in the system. When you program the system you assign each installed wireless sensor to a
relay using its hard coded address. Wireless sensors can be any of the following types:

Wireless Humidity Sensor (EA-WHS)

Wireless Temperature Sensor (EA-WTS)

Wireless Multi-Function Sensor (EA-WMFS): Any of the following wired sensors can be connected to the

wireless multi-function sensor, effectively converting the wired sensor to wireless:

Low temperature - blue thermistor probe

High temperature - red thermistor probes

Ultra Low temperature - white thermistor probes

WaterBug

®

sensor (supervised only)

Normally Open (N.O.) dry contact

Normally Closed (N.C.) dry contact

Wireless Supervision: EA800 wireless sensors are fully supervised for both communication drop-out

and low-battery condition. The AUX relay can be configured to give a low-battery indication (see

“Configuring the Relays” on page 34). The wireless sensor's assigned relay will change state if

communication drops out for more than 20 minutes.

Temperature Sensors

Table 5 lists the temperature sensors available for use with the EA800 Alarm System.

Table 5

EA800 Compatible Temperature Sensors

Model Number

Description

Operating Range/Parameters

TEMP-H-S

Thermistor, stainless steel probe,

high temperature sensor

32° F to 302° F

(0° C to 150° C)

TEMP-L-S

Thermistor, stainless steel probe,

low temperature sensor

-58° F to 158° F

(-50° C to 70° C)

TEMP-L-W

Thermistor, waterproof, low tempera-

ture sensor. For use in coolers and

freezers.

-58° F to 158° F

(-50° C to 70° C)

TEMP-H-W

Thermistor, waterproof, high tempera-

ture sensor

32° F to 221° F

(0° C to 105° C)