background image

4.

Scroll UP to display the default password “

001

5.

Press MODE to enter the password

6.

Scroll UP to the base frequency parameter which is “27” display will
show “P 27”

7.

Press MODE to display the current setting (will be either 50 or 60)

8.

Use the UP or DOWN keys to change the setting to the new value (either
50 or 60)

9.

Press MODE to store the new value

10. Drive will exit the program mode after it stores the new value

This procedure should be used only if the base frequency of the pump
drive motor is changed.

11. Alarm and Error Messages

If a fatal error has occurred while in Operational Mode, the error will flash on the
screen and the Red LED lamp will also flash. The menus can still be accessed by
holding down the menu key. This allows the user to try and fix the source of the
error if possible.

The following table gives an example of these messages and when you can
expect them to be displayed.

Message

Displayed When:

FATAL ERRORS: The pump and controller will not run while one of these error

conditions exists. The Red LED will blink and the error message will flash on the

screen. Users can access the menu system by pressing the MENU key. The

red LED and the message will cease when the error condition has been

corrected.

Analog Input # X

Out of Range

The analog input is less than 2.4 mA or greater

than 24 mA

ALARM

LEAK DETECT

The leak detection input has triggered

ALARM

LOW LEVEL

The level monitoring input has triggered

ALARM

AC DRIVE FAULT

Internal fault

ALARM

Motor e rror

The MPC has detected that the motor shaft is not

rotating at the expected speed

ALARM

CAM SE NSOR

MPC controller is not receiving correct signals from

the cam sensor in the pump eccentric box