Analog output calibration – Pulsafeeder MPC User Manual
Page 39
10.7.
Analog Output Calibration
1. The starting display will be:
S E T P T
X X . X X X
F L O W
X X . X X X
2. Press the MENU key
- M E N U -
C A L I B R A T I O N
3.
Press the ENTER key
C A L I B R A T I O N
P U M P F L O W
4. Press the UP ARROW key to access the analog output calibration
C A L I B R A T E D
A N A L O G O U T P U T
5. Press the ENTER key
S E T 0 % F L O W T O
0 4 . 0
M A
6. Use the UP and DOWN arrow keys to adjust the output signal as
required. The actual output signal will vary and can be monitored with a
meter or your facility control system. The value displayed on the screen
may not match the actual output signal and is for visual reference only.
7. Press the ENTER key once more to accept the calibration
S E T 1 0 0 % F L O W T O
2 0 . 0
M A
8. Use the UP and DOWN arrow keys to adjust as in step 6 above
9. Press the ENTER key once more to accept the calibration value
C A L B R A T I O N
A N A L O G O U T P U T
10. Analog output signal calibration is complete
11. Press the MENU key three times to exit back to the main operating
screen