6 analog input calibration, Analog input calibration – Pulsafeeder MPC User Manual
Page 36
10.6
Analog Input Calibration
If you are not using the 4-20mA input to the MPC for control, skip this
section. To calibrate the Input Current you must first correctly wire an
external signal source. Refer to the Control Input/Output Signal
Wiring Section (8.4.8). To perform a calibration, the signal-generating
device must be active and capable of generating the full range (low to
high) of potential input signals.
1. The starting display will be:
S E T P T
X X . X X X
F L O W
X X . X X X
2. Press the MENU key
- M E N U -
C A L I B R A T I O N
3. Press the ENTER key
C A L I B R A T I O N
P U M P F L O W
4.
Press the UP arrow key twice, to access the analog input calibration
C A L I B R A T I O N
A N A L O G I N P U T
5. Press the ENTER key
A P P L Y M I N M A
E N T E R T O S T A R T
6. Apply your desired minimum mA control signal to the MPC (usually 4
mA)
7. Press the ENTER key
M I N S E T P T X . X X M A
S P E E D
0 0 0 . 0 %