Power Wiring Information

Verify the correct supply voltage (115VAC or 230VAC) with the

nameplate affixed to your MPC. Ensure that your supply voltage
matches the MPC configuration.

Wires should be routed within the enclosure in a manner that

maintains separation between low voltage and extra-low voltage
conductors.

Applicable national and local electrical codes take precedence over

recommendations in the table below.


A circuit breaker or fuse must be provided as noted below.
Upon initial application of AC power, a current inrush will occur to

charge the DC bus capacitors. This is normal operation, and
breakers and other circuit protection devices should be sized
accordingly.

Power

Requirements

Recommended Minimum Wiring and Circuit Breaker

115 VAC Operation

230 VAC Operation

Actual

Draw

Circuit

Breaker

Wire

Size

Wire

Size

Safety

Approvals

1

Actual

Draw

Circuit

Breaker

Wire

Size

Wire

Size

Safety

Approvals

1

MPC and 0.25
Hp motor

7.0 A

10 A

14

AWG

2.5

mm

2

UL, CUL,

CE

3.5 A

10 A

14

AWG

2.5

mm

2

UL, CUL,

CE

MPC and 0.33
Hp motor

7.0 A

10 A

14

AWG

2.5

mm

2

UL, CUL,

CE

3.5 A

10 A

14

AWG

2.5

mm

2

UL, CUL,

CE

MPC and 0.5 Hp
motor

9.4 A

15 A

14

AWG

2.5

mm

2

UL, CUL,

CE

5.2 A

10 A

14

AWG

2.5

mm

2

UL, CUL,

CE

MPC and 0.75
Hp motor

16.8 A

25 A

12

AWG

4.0

mm

2

UL, CUL

9.4 A

15 A

14

AWG

2.5

mm

2

UL, CUL

MPC and 1.0 Hp
motor

16.8 A

25 A

12

AWG

4.0

mm

2

UL, CUL

9.4 A

15 A

14

AWG

2.5

mm

2

UL, CUL

MPC and 1.5 Hp
motor

24.2 A

35 A

10

AWG

6.0

mm

2

UL, CUL

12.2 A

20 A

14

AWG

2.5

mm

2

UL, CUL

Table 1 – Sizing Branch Circuits

Note 1: Applicable standards are Cenelec EN61326-1, UL61010-1, and CSA
C22.2#61010-1 and EN61010-1 3

rd

edition.

The MPC requires one connection to an external power source. It uses
this same connection to power its own supply, as well as the AC pump
motor. You must take all of these loads into consideration when sizing