(The mA value will be equal to your input signal level)
(The speed value is the setting the MPC will use for this signal value)
8. Press the ENTER key three times to step through the speed setting
value, most users will leave this at 000.0 %, however you an change it if
you wish using the UP and DOWN arrows.
9. Press the ENTER key once more to accept the calibration value
A P P L Y M A X M A
E N T E R T O S T A R T
10. Apply your desired maximum mA control signal to the MPC (usually 20
mA)
11. Press the ENTER key
M A X S E T P T X . X X M A
S P E E D
1 0 0 . 0 %
(The mA value will be equal to your input signal level)
(The speed value is the setting the MPC will use for this signal value)
12. Press the ENTER key three times to step through the speed setting
value, most users will leave this at 100.0 %, however you an change it if
you wish using the UP and DOWN arrows.
13. Press the ENTER key once more to accept the calibration value
A N A L O G I N P U T
C A L I B R A T E D
14. Analog input signal calibration is complete
15. Press the MENU key three times to exit back to the main operating
screen.
If you receive the following message:
C U R R E N T D E L T A
O U T O F R A N G E
This indicates that there is not a wide enough range between your maximum
and minimum analog signals. The minimum signal range is 3 mA. The most
likely source of this error is the user did not change the value of the incoming
analog signal when moving from the MIN calibration to the MAX calibration.