Lyntec RPC User Manual
Page 50

139-0498-01.50
Appendix B
50
GET /p2.rpc?IPE001=1
This control string will turn event #1 on.
GET /p2.rpc?IPE001=0
This control string will turn event #1 off .
Events include:
Event 1 = “All Breakers ON”
Event 2 = “All Breakers OFF”
Event 3 = “Hurry OFF” zips all breakers off fast.
Event 4 = “EO” Emergency override
Event 5 = “Audio Timer” (future)
Event 6 = “BO” Brown-Out
Event 7 = “DMX”
Verifi cation Scheme:
The following GET command will return the current status of all
breakers, zones and events in the RPC system.
GET /p2.rpc
The system will return the following:
breakers=10110111111111111111
zones=111111111011 events=1000000
The above return is displaying the status of a 20 circuit breakers
system in which all are presently ON, with the exceptions of
breaker #2 and breaker #5, which are OFF.
The above return is also showing the status of 12 zones, all are
ON with the exception of zone #10, which is OFF.
The events return is showing that event #1 is active = “All
Breakers ON”
Status returns for
Breakers:
Status returns for Zones
and Events:
0 = OFF
0 = OFF
1 = ON
1 = ON
2 = Breaker Tripped
2 = Processing
3 = Faulty
4 = Empty
Events Control = E