Lyntec RPC User Manual
Page 39

139-0498-01.39
39
Appendix A
1. If RPS Slave panels are being used in conjunction with an
RPC Master panel, install and connect one 18 AWG six (6) 
conductor (Belden 27600 A or equivalent) or two 18-24 AWG 
twisted pairs for data and one 16-18 AWG for power per RPS 
unit. Terminate the Left Bus B, Left Bus A, Right Bus B, Right 
Bus A, Common (–) and 24VDC (+) in the screw-terminal 
header for that RPS (Slave Panel 2 – 4) from left to right.
2. At the RPS Slave panels, strip the cable sheath back
approximately 20 inches. Cut the conductors for Left Bus 
B, Left Bus A, – and + down to approximately 4 inches and 
terminate them in the Left Bus screw-terminal header from 
left to right. Terminate the remaining two conductors in 
the Right Bus B and Right Bus A positions of the Right Bus 
screw-terminal header.
3. Using two cut lengths of 18 AWG wire, install jumpers from
Left Bus – and + to Right Bus – and +. Right Bus will not 
operate without these jumpers installed to provide 24VDC 
power and common.
4. Set the slave address selectors as follows:
Left Control Bus
Right Control Bus
Panel #2
2
3
Panel #3
4
5
Panel #4
6
7
Table A-1