Lyntec RPC User Manual
Page 16

139-0498-0116
Chapter Four--Wiring
16
Emergency Shutdown Wiring:
To connect your fi re alarm or emergency management system 
to the RPC, follow these steps.
1. From the fi re alarm unit or latching Emergency Shutoff
switch, wire the Normally Open (NO) contacts to the IN and 
24V positions of Digital I/O Port #1 on the Controller. 
2. If a remote status indicator is used, ensure that the positive
terminal is wired to the 24V position and the negative 
terminal is wired to the OUT position of Digital I/O Port #1.
3. When the Normally Open contacts are closed, the status
indicator should immediately light and all breakers that 
have been selected for E. Shutoff should cycle to OFF.
4. When the contacts are released, the status indicator should
extinguish and all breakers that were ON when E. Shutoff 
was activated should return to the ON state.
See Chapter 5 to confi gure the software for emergency 
shutdown.
Figure 4-4: Emergency shutdown 
wiring
Normally Open
Fire Alarm Contacts
24 VDC LED
Status Indicator
1
2
3
4
5
6
Left Bus
IN
24V
OUT
Digital I/O
OFF
