Appendix B
Deactivate breakers
0xB0, 0xB5, breaker_address_1, …, breaker_address_n, 0xF0
breaker_address_1, …, breaker_address_n – addresses of reakers
to be deactivated n<=168
Activate/deactivate breakers
0xB0, 0XB5, breaker_address_1, …, breaker_address_m, 0xB6,
breaker_address_1, …, breaker_address_n, 0xF0
breaker_address_1, …, breaker_address_m – addresses of
breakers to be activated breaker_address_1, …, breaker_
address_n – addresses of breakers to be deactivated m+n<=168
Request all breakers status
0xB0, 0xB6, 0xF0
Request breakers status
0xB0, 0xBD, breaker _address_i, breaker _address_j, …, breaker
_address_n, 0xF0
breaker_address_1, …, breaker_address_n – addresses of
breakers, status of which is requested
Request bus status
0xB0, 0xBE, bus, 0xF0
bus=0-7 – number of bus, status of which is requested
Reply to activate/deactivate breakers command: status of
updated breakers
0xB0, 0xC8, breaker_address_i, breaker_status_i, breaker_address_j,
breaker_status_j, …, breaker_address_n, breaker_status_n, 0xF0
breaker_address_i, breaker_status_i, breaker_address_j,
breaker_status_j, …, breaker_address_n, breaker_status_n
Addresses and status of breakers updated by the command reply
is generated for