1
Make sure that the panel(s) have
been wired by a certifi ed electrician
and that there is power to the
panel(s).
Confi rm that RPS (slave) panels
are connected to the master as
indicated in the “RPC to RPS Wiring
Instructions” bulletin.
2 Confi rm that the electrician has
connected the 15A breaker in the
master panel (position 21) to the
power supply in the lower sidecar.
3 Once the 15A breaker is connected
and switched on, confi rm that the
orange power LEDs on each circuit
board are lit.
Control Board
I/O Expander
Board
Multi-Panel Expander
Board
POWER LEDS
If LEDs do not light, check chapter
4 of the RPC manual to see that
circuit boards are connected
properly.
4 Connect a computer to the control
board using a CAT5 crossover
cable OR connect the RPC to your
network.
If connecting via a crossover cable:
With a computer directly connected
to the RPC through the Ethernet
port, change the computer’s IP
address manually so it is in the same
default IP subnet that the RPC uses:
192.168.1. The default IP address of
the RPC is 192.168.1.250.
Ethernet Port
Yellow
Buttons
LCD
Screen
If connecting via a network:
Connect the RPC to the network via
the Ethernet port. Push the upper
yellow button twice or until the IP
address appears on the LCD screen.
OVER
Panel Neutral Bus
Panel Ground Bar
Power Supply DC –
Controller Cable
Controller Cable
Power Supply DC +
N L
+ + – –
Transducer Neutral
Transducer Load
15A Breaker