beautypg.com

Installation, Oven location and ventilation – Blodgett CNVX-14E User Manual

Page 9

background image

5

Installation

Oven Location and Ventilation

OVEN LOCaTION
The well planned and proper placement of your oven will

result in long term operator convenience and satisfactory

performance.
Certain minimum clearances must be maintained be-

tween the oven and any combustible or non-combustible

construction. See the table below.
In addition, the following clearances are recommended

for servicing.
• Oven body sides - 12” (30cm)
• Oven body back - 12” (30cm)
NOTE: On gas models, routine servicing can usually

be accomplished within the limited movement

provided by the gas hose restraint. If the oven

needs to be moved further from the wall, the

gas must first be turned off and disconnected

from the oven before removing the restraint.

Reconnect the restraint after the oven has been

returned to its normal position.

Left Side Heat Shield
Heat sources should not be near the air vents located on

the left hand side of the gas appliance.

OVEN

MOdEL

MINIMUM REQUIREd

CLEaRaNCES

Right Side

Left Side

Back

BCX-14G

CNVX-14G

1”

(25.4mm)

6”

(152.4mm)

6”

(152.4mm)

BX-14G

1”

(25.4mm)

0”

(0mm)

6”

(152.4mm)

BCX-14E

BX-14E

CNVX-14E

2”

(50.8mm)

2”

(50.8mm)

3”

(76.2mm)

VENTILaTION
The necessity for a properly designed and installed venti-

lation system cannot be over emphasized. The ventilation

system will allow the unit to function properly while remov-

ing unwanted vapors and products of combustion from

the operating area.
The appliance must be vented with a properly designed

mechanically driven exhaust hood. The hood should be

sized to completely cover the equipment plus an over-

hang of at least 6” (15 cm) on all sides not adjacent to a

wall. The capacity of the hood should be sized appropri-

ately and provisions made for adequate makeup air.

WaRNING!!

Failure to properly vent the oven can be haz-

ardous to the health of the operator; and will

result in operational problems, unsatisfactory

baking, and possible damage to the equip-

ment. damage sustained as a direct result of

improper ventilation will not be covered by the

Manufacturer’s warranty.

When installed in the Commonwealth of Massachusetts,

this appliance must be interlocked with the hood exhaust

system so that the appliance may be operated only when

the hood exhaust system is running.
U.S. and Canadian Installations
Refer to your local ventilation codes. In the absence of

local codes, refer to the National ventilation code titled,

“Standard for the Installation of Equipment for the Remov-

al of Smoke and Grease Laden Vapors from Commercial

Cooking Equipment”, NFPA-96- Latest Edition.
General Export Installations
Installation must conform with Local and National instal-

lation standards. Local installation codes and/or require-

ments may vary. If you have any questions regarding the

proper installation and/or operation of your unit, please

contact your local distributor. If you do not have a local

distributor, please call Blodgett Combi at 0011-802-658-

6600.

This manual is related to the following products: