Appendix D. The Public Table

Control Parameters When Troubleshooter is Running

TimeSeries(1) Writing this variable will force a Vibrating Wire

measurement and create the TimeSeries.bin and

spectrum.bin files.

Example:

101 = measures AVW200 chan1 and Mux chan1

102 = measures AVW200 chan1 and Mux chan2

.....

201 = measures AVW200 chan2 and Mux chan1

202 = measures AVW200 chan2 and Mux chan2

....

232 = measures AVW200 chan2 and Mux chan32

Notes: TimeSeries(2)..(4) need to be filled with valid

values before making the measurement.

TimeSeries(2) Begin Frequency for force measurement (100 - 6500)
TimeSeries(3) Eng Frequency for forcing measurement (100 - 6500)
TimeSeries(4) Excite voltage for forcing measurement (1=5volts or

2=12volts)

TimeSeries(5) Copy of the Chan/MuxChan executed in TimeSeries(1)
TimeSeries(6) Measured Frequency (Hz)
TimeSeries(7) Measured Amplitude (MVolts_RMS)
TimeSeries(8) Measured Signal-to-Noise Ratio
TimeSeries(9) Measured Noise Freq (Hz)
TimeSeries(10) Measured Decay Ratio
TimeSeries(11) Measured Thermistor (ohms)

D-3