AVW200-series 2-Channel Vibrating Wire Spectrum Analyzer Modules

1.3.1.1 PakBus Protocol/Direct RS-232 Connection

When using the PakBus protocol, the AVW200() instruction in CRBasic

supports an AVW200 connected to a datalogger via a cable attached to the

AVW200’s RS-232 port. You can run the datalogger AVW200() instruction in

either the pipeline or sequential mode. This instruction is contained in the

following datalogger operating systems:

CR800std.06 or greater

CR1000std.15 or greater

CR3000std.08 or greater

Multiplexers can be controlled by either the AVW200 or the datalogger.

Read more! You can find Quick Start Guides in Section 3, AVW200()

instruction description in Section 6.1, and programming examples in

Section 7.

1.3.1.2 PakBus Protocol/Wireless Connection

An AVW206, AVW211, or AVW216 interface can transmit data to a

corresponding spread spectrum radio that is attached to the datalogger. The

AVW200() instruction in CRBasic supports these wireless interfaces. You can

run the AVW200() instruction in either the pipeline or sequential mode. This

instruction is contained in the following datalogger operating systems:

CR800std.06 or greater

CR1000std.15 or greater

CR3000std.08 or greater

Multiplexers can be controlled by the wireless AVW200.

Read more! You can find Quick Start Guides in Section 3, AVW200()

instruction description in Section 6.1, and a programming example in

Section 7.1.2.

1.3.1.3 PakBus Protocol/MD485 Communication

For situations where wireless communication is impractical, MD485 multidrop

modems may extend the distance between the AVW200 interfaces.

Multiplexers must be controlled by the AVW200.

Read more! Appendix I describes using MD485 modems with AVW200s.

1.3.1.4 SDI-12 Communication Mode

SDI-12 is the only option available for our CR5000, CR10X, and CR23X

dataloggers and non-Campbell Scientific dataloggers. Our CRBasic

dataloggers use the SDI12Recorder instruction and Edlog dataloggers (i.e.,

CR10X, CR23X) use Instruction 105. The SDI12Recorder instruction should

only be run in the sequential mode. When using SDI-12, multiplexers must be

controlled by the datalogger.

Read more! You can find a Quick Start Guide in Section 3.3.1,

SDI12Recorder instruction description in Section 6.2, and a programming

example in Section 7.5.

4