Appendix I. Using MD485 Multidrop Modems with AVW200 Interfaces

FIGURE I-4. MD485 and its connectors.

I.2.1 Datalogger to MD485

The 18663 Null Modem Cable is used to connect an MD485 with the CR800,

CR850, CR1000, or CR3000 datalogger. One end of the null modem cable

attaches to the RS-232 port on the MD485, and the other end attaches to the

RS-232 port on the datalogger (see FIGURE I-4).

I.2.2 MD485 to MD485

The connection between MD485s is made with a CABLE2TP two-twisted pair

cable with shield. Insulation colors are red/back and green/white. One pair is

used for the differential data (“A” connects to “A”, “B” connects to “B”), and

one line of the other twisted pair is used for the signal ground (third connection

on the MD485 terminal block). This is shown in FIGURE I-4 and FIGURE

I-5. The cable shield should be connected to a chassis or earth ground (NOT

the signal ground) at one end as shown in FIGURE I-5.

Connects to another MD485 via

the CABLE2TP

Connects to earth ground

via an 8 AWG wire

Connects to the datalogger’s

RS-232 port or the AVW200’s

RS-232 port via a null modem cable

I-3