Avw200() instruction controlling two multiplexers, 2. wiring for example 7.2 – Campbell Scientific AVW200-series Vibrating Wire Interfaces User Manual

Page 55

background image

AVW200-series 2-Channel Vibrating Wire Spectrum Analyzer Modules

'Calculate displacement (inches) from Digits and calibration polynomial

PSI=2.49866e-10*Digits^2 + 8.716e-5*Digits + -.2

NextScan

EndProg

7.2 AVW200() Instruction Controlling Two Multiplexers

TABLE 7-2 shows wiring used for this example. This program measures 16

sensors on each multiplexer.

TABLE 7-2. Wiring for Example 7.2

Datalogger Port for

Cable Attachment

Cable Needed to

connect to AVW200

AVW200 Port or

Model

COM1 (control port

pairs C1/C2)

17855 Cable (pigtail to

DB9 male cable)

RS-232

'CR1000

'Declare Variables and Units

Public BattV

Public PTemp_C

'Public Temp_C

Public Data1, Data2

Public Mux1(16,6), Mux2(16,6)

Units BattV=Volts

Units PTemp_C=Deg C

'Define Data Tables

DataTable(VWTable1,True,-1)

DataInterval(0,90,Sec,10)

Sample (96,Mux1(),IEEE4)

Sample (96,Mux2(),IEEE4)

Minimum(1,BattV,FP2,False,False)

EndTable

'Main Program

BeginProg

SerialOpen (Com1,38400,0,0,0)

Scan(90,Sec,1,0)

AVW200(Data1(),Com1, 200, 200, mux1(1,1),1,1,16,450,3000,2,_60HZ,1,0)

AVW200(Data2(),Com1, 200, 200, mux2(1,1),2,1,16,450,3000,2,_60HZ,1,0)

Battery(BattV)

PanelTemp(PTemp_C,_60Hz)

CallTable(VWTable1)

NextScan

EndProg