AVW200-series 2-Channel Vibrating Wire Spectrum Analyzer Modules

3.2 Multiplexers Controlled by AVW200

3.2.1 Direct RS-232 Connection

Cable that Comes with Sensor

CABLE4CBL-L Four Conductor Cable

17855 Pigtailed Cable or

18663 Null Modem Cable

19246 Power Cable

Multiplexer

AVW200

Multiplexer

Datalogger

Power

Supply

Sensors

Sensors

For this example configuration, vibrating wire sensors are attached to

multiplexers, which are controlled by the AVW200. The AVW200 is

connected directly with the datalogger.

The following steps are used:

1. If you are not using the default multiplexer, go to the

Deployment/Measurement tab in DevConfig and select the multiplexer

you are using (Section 5.1, Connecting to DevConfig, and Section 5.2.1,

Communications). The default multiplexer for the AVW200 is the

AM16/32A.

2. Attach the multiplexers to the AVW200 as shown in FIGURE 4-4.

3. Connect the sensors to the multiplexers.

Read more! Information about connecting the vibrating wire sensors to

the multiplexer is provided in the AM16/32B manual.

4. Use the 17855 cable to attach the AVW200 to control port pairs on the

datalogger, or use the 18663 Null Modem cable to attach the AVW200 to

the RS-232 port on the datalogger.

5. Connect one end of the 19246 power cable to the 12V and G terminals on

the AVW200 and the other end to the 12V and G terminals on the

datalogger or external power supply.

Read more! You can find power and ground connection information in

Section 4.2 and datalogger connection information in Section 4.3.

6. Create a CRBasic program that includes the AVW200() instruction for

each of the multiplexers that the AVW200 will control.

14