beautypg.com

Step 4 wiring the controller, Wiring connections, 21 tbb – Red Lion DLC User Manual

Page 6

background image

6

9

5

8

6

7

10

4

3

TBA

12

+24VDC OUT

DC+ / (AC)

DC- / (AC)

OUTPUT COMMON

OP1

AL1

AL2/OP2

+

-

Load

Load

Load

+

-

-

+

-

+

(200 mA max)

Load Power from DLC

External Controller Power

CH A = Terminals 5, 6, & 7

CH B = Terminals 8, 9, & 10

Load

+

9

Load

+

-

+

TBA

+24VDC OUT

DC- / (AC)

DC+ / (AC)

OUTPUT COMMON

1

2

3

4

-

5

8

6

OP1

AL1

Load

+

-

-

7

10

AL2/OP2

-

+

Separate External Power

For Load and Controller

Load

+

9

Load

+

-

+

TBA

+24VDC OUT

DC- / (AC)

DC+ / (AC)

OUTPUT COMMON

1

2

3

4

-

5

8

6

OP1

AL1

Load

+

-

-

7

10

AL2/OP2

Combined External Power

For Load and Controller

CONTROL AND ALARM OUTPUT CONNECTIONS

CH A = Terminals 5, 6, & 7

CH B = Terminals 8, 9, & 10

CH A = Terminals 5, 6, & 7

CH B = Terminals 8, 9, & 10

* For two wire RTDs, install a copper sense lead of the same gauge and length as the RTD leads. Attach one end of the wire at the probe and the other end to input

common terminal. Complete lead wire compensation is obtained. This is the preferred method. If a sense wire is not used, then use a jumper. A temperature offset
error will exist. The error may be compensated by programming a temperature offset.

** +24 VDC OUT (Terminal 3) shares common with Ch A Inputs & All Control/Alarm Outputs.

0-10V, 0-20mA

RTD EXC.

TC+ OR RTD

INPUT COMMON

5

2

3

6

1

4

TBB

Exc./

Jumper

Sense

Sense

RTD and Resistance

*

CH A = Terminals 4, 5 & 6
CH B = Terminals 1, 2 & 3

4

TBB

1

2

5

TC+ OR RTD

INPUT COMMON

3

6

RTD EXC.

0-10V, 0-20mA

TC+

TC-

Thermocouple and Millivolt

CH A = Terminals 4, 5 & 6
CH B = Terminals 1, 2 & 3

2

1

TBB

DC-

DC+

INPUT COMMON

TC+ OR RTD

45

3

0-10V, 0-20mA

6

RTD EXC.

Voltage or Current

CH A = Terminals 4, 5 & 6
CH B = Terminals 1, 2 & 3

2

TBB

TC+ OR RTD

INPUT COMMON

4

1

5

RTD EXC.

0-10V, 0-20mA

3

6

+24VDC OUT

(200 mA max)

LOAD

TBA

3

+

-

2 Wire Current Signal Requiring DLC Excitation **

CH A = Terminals 4, 5 & 6
CH B = Terminals 1, 2 & 3

(200 mA max)

+24VDC OUT

TC+ OR RTD

RTD EXC.

0-10V, 0-20mA

INPUT COMMON

LOAD

TBA

3

TBB

1

2

45

3

6

Vs

Out

Comm

3 Wire Current or Voltage Signal Requiring DLC Excitation **

CH A = Terminals 4, 5 & 6
CH B = Terminals 1, 2 & 3

INPUT CONNECTIONS

STEP 4 WIRING THE CONTROLLER

(AC)

(AC)

TBA

2

1

~

~

1

TBA

DC+

DC-

2

-
+

24 VAC POWER

18 to 36 VDC POWER

WIRING CONNECTIONS

All conductors should meet voltage and current ratings for each terminal. Also, cabling should conform to appropriate standards of good installation, local codes

and regulations. When wiring the controller, use the numbers on the label to identify the position number with the proper function. Strip the wire, leaving
approximately 1/4" (6 mm) of bare wire exposed. Insert the wire into the terminal, and tighten the screw until the wire is clamped tightly. (Pull wire to verify
tightness.) Each terminal can accept up to one #14 AWG (2.55 mm), two #18 AWG (1.02 mm), or four #20 AWG (0.61 mm) wires.

CONTROLLER POWER CONNECTIONS

For best results, the power should be relatively “clean” and within the

specified limits. Drawing power from heavily loaded circuits or from circuits
that also power loads that cycle on and off should be avoided. It is recommended
that power supplied to the controller be protected by a fuse or circuit breaker.