beautypg.com

Step 13 programming the alarms, Alarm action figures – Red Lion DLC User Manual

Page 12

background image

12

STEP 13 PROGRAMMING THE ALARMS

Alarm 1 and 2: The controller is equipped with two alarms for each channel. The status of these alarms

can be read through AL1 registers 40015/40031 and AL2 registers 40016/40032.

Action (40131/40231), (40136/40236): Select the action for the alarms. See Alarm Action Figures for a

visual explanation.
Manual: In Manual mode, the alarms are forced on and off by writing ‘0’ or ‘1’ to the appropriate

alarm output register. In this mode, the alarms will not respond to Alarm and Hysteresis Values.

Absolute HI (balanced or unbalanced hysteresis): The alarm energizes when the Process Value exceeds

the alarm.

Absolute LO (balanced or unbalanced hysteresis): The alarm energizes when the Process Value falls

below the alarm.

Deviation HI, Deviation LO, Band Acting: In these actions, Alarm 1 and 2 value tracks the Setpoint

value.

Cooling (OP2): For heat/cool applications, select Cool for Alarm 2. The controller then utilizes the

Alarm 2 output as the Cooling Output (OP2). If cooling is selected, the remaining Alarm 2
parameters are not available.

OFF

ON

AL + ½Hys

AL

AL - ½Hys

OFF

Absolute High Acting (Balanced Hys)

Hys

TRIGGER POINTS

ALARM

STATE

OFF

ON

AL + ½Hys

AL

AL - ½Hys

OFF

Absolute Low Acting (Balanced Hys)

TRIGGER POINTS

Hys

ALARM

STATE

ALARM
STATE

OFF

ON

Hys

SP + AL

SP

OFF

TRIGGER POINTS

Deviation High Acting (AL > 0)

ALARM

STATE

Hys

SP - AL

SP

SP + AL

Hys

TRIGGER POINTS

ON

OFF

OFF

ON

ON

Band Inside Acting

ALARM
STATE

OFF

ON

Hys

SP - AL

SP

OFF

TRIGGER POINTS

Deviation Low Acting (AL > 0)

ALARM
STATE

OFF

ON

Hys

AL

AL - Hys

OFF

TRIGGER POINTS

Absolute High Acting (Unbalanced Hys)

ALARM
STATE

OFF

ON

Hys

AL + Hys

AL

OFF

TRIGGER POINTS

ALARM
STATE

ON

OFF

Hys

SP + (-AL)

SP

ON

TRIGGER POINTS

Deviation High Acting (AL< 0)

ALARM

STATE

ON

Hys

SP - AL

SP

OFF

SP + AL

ON

Hys

OFF

OFF

TRIGGER POINTS

ALARM ACTION FIGURES

Note: Hys in the above figures refers to the Alarm Hysteresis.

Value (40003/40019), (40004/40020): The alarm values are entered as process units or degrees.
Hysteresis (40134/40234), (40139/40239): The Hysteresis Value is either added to or subtracted from the alarm value, depending on the alarm action selected.

See the Alarm Action Figures for a visual explanation of how alarm actions are affected by the hysteresis.

Trigger Points: Trigger points are the Process Values where the alarm state changes. Their values cannot be entered directly, but are shown as a reference in the

SFDLC software. The alarm value, hysteresis value, and setpoint alarm type determine the trigger points. With Deviation or Band actions, the alarm value and
setpoint value are combined to determine the trigger points. Trigger points must not be greater than +32000 or less than -32000. If these limits are exceeded,
the alarm may not function properly.

Reset (40132/40232), (40137/40237): The alarms can be programmed for Automatic or Latched. In Automatic mode, an energized alarm turns off automatically

once the Process Value leaves the alarm region. In Latched mode, an energized alarm requires a manual reset. This is done by writing ‘0’ to the appropriate
output status register. After writing ‘0’, the Automatic or Latched alarm will not turn on again until after the Process Value first returns to the alarm off region.
Only alarms configured for Manual action can be energized by writing a ‘1’ to its’ alarm output status register.

On Delay (40135/40235), (40140/40240): The time, in seconds, required for the Process Value to be in the alarm region before the alarm will activate. It is used

to allow temporary or short excursions into the alarm region without tripping the alarm.

Enable Standby Delay (40133/40233), (40138/40238): Standby prevents nuisance (typically low level) alarms after a power up or setpoint change. After

powering up the controller or changing the setpoint, the process must leave the alarm region. Once this has occurred, the standby is disabled and the alarm
responds normally until the next controller power up or setpoint change.