beautypg.com

Dlc register table – Red Lion DLC User Manual

Page 23

background image

23

DLC REGISTER TABLE

The below limits are shown as Integers or HEX < > values. Read and write functions can be performed in either Integers or Hex as long as the conversion was done

correctly. Negative numbers are represented by two’s complement.

Note 1: The DLC should not be powered down while parameters are being changed. Doing so may corrupt the non-volatile memory resulting in checksum errors.

REGISTER

ADDRESS

1

REGISTER NAME

LOW LIMIT

2

HIGH LIMIT

2

FACTORY

SETTING

3

ACCESS

COMMENTS

CH A

CH B

CONTROLLING VALUES

40001

40017

Process Value

N/A

N/A

N/A

Read Only

40002

40018

Setpoint Value

-32000

32000

0

Read/Write

Limited by Setpoint Limit Low and Setpoint Limit High.

40003

40019

Alarm 1 Value

-32000

32000

0

Read/Write

40004

40020

Alarm 2 Value

-32000

32000

0

Read/Write

PID PARAMETERS

40005

40021

Output Power

0 or -1000

1000

0

Read/Write

40006

40022

Setpoint Deviation

N/A

N/A

N/A

Read Only

40007

40023

Proportional Band

0

9999

40

Read/Write

0 = On/Off Control, 1 = 0.1%

40008

40024

Integral Time

0

9999

120

Read/Write

0 = Off, 1= 1 second

40009

40025

Derivative Time

0

9999

30

Read/Write

0 = Off, 1= 1 second

40010

40026

Offset Power

-1000

1000

0

Read/Write

1 = 0.1%; Applied when Integral Time is 0.

40011

40027

Auto-Tune Start

0

1

0

Read/Write

0 = Stop, 1 = Start; Mirror of Coil 16/28.

40012

40028

Auto-Tune Phase

N/A

N/A

N/A

Read Only

0 = Off, 4 = Last phase during Auto-Tune

40013

40029

Auto-Tune Code

0

2

0

Read/Write

0 = Fastest response, 2 = Slowest response

OUTPUT STATUS

40014

40030

Control Output OP1

N/A

N/A

N/A

Read Only

0 = Off, 1 = On; Mirror of Coil 9/21.

40015

40031

Alarm Output AL1

0

1

0

Read/Write

40016

40032

Alarm Output AL2 / OP2

0

1

0

Read/Write

CONTROL STATUS

40041

40049

Control Mode

0

1

0

Read/Write

0 = Automatic, 1 = Manual; Mirror of Coil 12/24.

40042

40050

Disable Setpoint Ramping

0

1

0

Read/Write

0 = Enabled, 1 = Disabled; Mirror of Coil 13/25.

40043

40051

Setpoint Ramping In Process

N/A

N/A

N/A

Read Only

0 = No, 1 = Yes; Mirror of Coil 14/26.

40044

40052

Disable Integral Action

0

1

0

Read/Write

0 = Enabled, 1 = Disabled; Mirror of Coil 15/27

40046

40045

40053

Remote / Local Setpoint Select

Ramping Setpoint Value

0

N/A

1

N/A

0

N/A

Read/Write

Read/Write

SETPOINT CONTROLLER MODEL ONLY

PROFILE OPERATION

40065

Profile Operating Status

0

3

0

0 = Off; 1 = Abort; 2 = Run/Start, 3 = Pause, 4 = Error
Delay (status only - writing a “4” will revert unit to mode
“3” Pause)

40066

40074

Profile Phase

N/A

N/A

N/A

Read Only

0 = Ramp; 1 = Hold

40067

40075

Profile Segment

N/A

N/A

N/A

Read Only

40068

40076

Profile Phase Time Remaining

1

9999

N/A

Read/Write

40069

40077

Profile Cycle Count Remaining

1

250

0

Read/Write

40070

40078

Advance Profile Phase

0

1

0

Read/Write

INPUT PARAMETERS

40198

Ch B Assignment

0

1

0

Read/Write

0 = PID, 1 = Remote Setpoint

40199

0

2

0

Read/Write

40103

40102

40101

40203

40202

40201

Resolution

Temperature Scale

Input Type

0

0

0

1

1

17

0

0

2

Read/Write

Read/Write

Read/Write

0 = °F, 1 = °C, For Input Types 0-11.

See Input Listing

1 = 0.1%, 0.0 = Off; Limited by Power Low Limit and
Power High Limit in Automatic Control Mode. Negative
percent is cooling (direct) available when AL2 is
Cooling. Write only possible during Manual mode.

Deviation = Process Value - Setpoint Value; During
Auto-Tune: Process Value - Auto-Tune Setpoint Value

0 = Off, 1 = On; A write of 1 is only possible when
alarm is set for Manual. Mirror of Coil 10/22.
0 = Off, 1 = On; A write of 1 is only possible when
alarm is set for Manual. Mirror of Coil 11/23.

(0 = Stop, 1-20 = Current Segment)

1

For Input Registers, replace the 4xxxx with a 3xxxx in the above register address. The 3xxxx are a mirror of the 4xxxx Holding Registers.

2

An attempt to exceed a limit will set the register to its high or low limit value.

3

See MODBUS Calibration for procedure on restoring Factory Settings.

1 = Advances “running” Profile to next ramp or hold
phase

0 = Local Setpoint, 1= Remote Setpoint

Actual Setpoint Value used for control (ramps when
ramping enabled.) Limited by Setpoint Limit Low and
Setpoint Limit High.

40073

Read/Write

(0-3 only)

1= 0.1 Minute; Can make temporary change on the fly
Value Over-range = 32003 (may occur on extremely
slow ramp; Ramp will function properly)
0-250; If Cycle Count (40326/40426) is 250
(Continuous operation), value will reset to 250 at 0.

Local / Remote Setpoint
Transfer Mode

0 = Normal (Output may bump)
1 = Auto (Output may bump)
2 = Track (Local Setpoint assumes value of Remote SP
for Remote to Local Transfer)

Input Types 0-12 0=Low (x1) whole input units, 1
= High (x10) tenth of input units, Input Type 13 0 = 0.1
mV, 1 = 0.01 mV, Input Types 14-15, N/A

Process value of present input level. This value is
affected by Input Type, Resolution, & Scaling. In
Square Root Extraction Modes, the Process Value will
read zero for inputs below 0.1% of full scale.