Show Analog Output Status
The AOUT command shows the following information:
- Analog out mode is the output mode for the channel, for example
0 ... 10 V.
- Error level is the level that the analog output is set to in case of
transmitter error.
- Status indicates the current status of the channel. The statuses are
- ON: Normal measurement operation.
- OFF: No quantity selected for the channel using the ASEL
command. See section Set/show Analog Output Quantity and
- ERROR: Transmitter error, channel set to error level.
- TEST: Analog channel being tested using the ATEST command.
See section Test Analog Outputs on page 40.
AOUT
Example:
>aout
*** ANALOG OUTPUT 1 ***
Ch1 Analog out mode : 4_20MA
Ch1 Notification : ON
Ch1 Error level : 3.6
Ch1 Status : ON
Ch1 Quantity : RH
RH lo : 0
RH hi : 100
RH : 23.32 %
Current : 7.73 mA
*** ANALOG OUTPUT 2 ***
Ch2 Analog out mode : 4_20MA
Ch2 Notification : ON
Ch2 Error level : 3.6
Ch2 Status : ON
Ch2 Quantity : T
T lo : -60
T hi : 100
T : 23.66 'C
Current : 12.37 mA
>