4-48

Library Operation

Troubleshooting

Do not know the
administration menu
password.

Try the default password (000-000-000). If that is not accepted,
call a service representative.

Cartridge inserted in the
mailslot, but

LOAD ERROR

or

FAILED

displays.

Press

CANCEL

and try to insert the cartridge in the mailslot

again. See “Loading Cartridges Into the Library” on page 4-14
for the correct tape loading orientation. If this does not work,
verify that the correct tape type is being used. (See “Choosing
Tape Cartridges” on page 3-3.)

If the light bar on the front panel is orange, cycle power to the
library and try to load the cartridge again when the drive
numbers and status indicators display.

If the cartridge is in the mailslot correctly and a

LOAD ERROR

or

FAILED

message still displays, this could indicate a library

failure. Call a service representative.

Cartridge inserted in the
mailslot, but

TRANSPORT

FULL

displays.

The cartridge transport mechanism already contains a tape
cartridge. Consult your software package documentation. A
service call may be needed.

Cartridge removal
attempted, but an

EJECT

ERROR

message displays.

Press

CANCEL

and try ejecting the cartridge again. See

“Removing Cartridges from the Library” on page 4-19.

If the light bar on the front panel is orange, cycle power to the
library and try to eject the cartridge again when the drive
status displays (“ready” state).

If there is not a cartridge in the mailslot and an

EJECT

ERROR

message still displays, this could indicate a library

failure. Call a service representative.

Cartridge removal
attempted, but a

RESERVED

message displays.

The host may have reserved the element and must unreserve
it. Refer to the host system documentation to unreserve a
tape.

A security configuration was set to prevent cartridge removal.
See “SECURE ON/OFF” in Table 4-8 on page 4-28.

Started a test and need to
stop.

Press

CANCEL

. The current test loop continues until finished,

then the test stops.

Table 4-14

Troubleshooting (Continued)

Problem

Solution