Web interface 9

Parameter

Function

Server Intake Temperature

Displays the average server intake temperature

Server Exhaust Temperature Displays the average server exhaust temperature
Cooling

Displays the heat removed by the water

Water Inlet Temperature

Displays the temperature of the water coming into the

MCS unit to be used to cool the servers

Water Outlet Temperature

Displays the temperature of the water after removing
the server heat

Water Flow

Displays the water flow rate in liters or gallons per

minute

Water Valve

Displays the percentage of the water valve opening

Water System Integrity

Displays the Leak Detected Alarm, the Condensation

Pump Warning, and condensation pump activity:

Cycles—Displays the number of times the pump

runs

Duration—Displays the total amount of time the

pump has run since it was last activated

Fan Speed Target

Displays the fan speed level from 0 to 100%:

0%= Fan turned off

100%= Fan at maximum speed

Intake Temperature Details

Displays the intake temperature from top to bottom

Exhaust Temperature Details Displays the exhaust temperature from top to bottom
Fans (Top to Bottom)

Displays the fans installed and the rate per minute

(rpm)

Magnetic Door Lock Status

Displays the door lock status:

OKThe door lock is functioning properly and the

doors are closed.

Doors ReleasedEither the front or back door is

open.

Dew point monitoring

Displays humidity level inside the rack cabinet,

calculated dew point, and rack door status