Cooling performance parameter settings 42

Parameter

Function

Low Temperature
Threshold

Used to issue a warning if the low temperature threshold

temperature is exceeded

Water Flow Loss
Emergency Door

Opening
Temperature

Threshold

Used to open the HP Modular Cooling System doors when
the temperature threshold is exceeded and water loss is

detected.

This value cannot be lower than 5°C (41°F) above or more
than 20°C (68°F) above the Server Intake Temperature Set

Point.

High Temperature
Emergency Door

Opening Threshold

Used to open the MCS doors when the temperature

threshold is exceeded.
This value:

Cannot be lower than 5°C (41°F) above or more than
20°C (68°F) above the Server Intake Temperature Set

Point

Cannot be less than the Water Flow Loss Emergency

Door Opening Temperature Threshold

Excessive
Moisture:

Condensation
Pump Cycles

Warning Threshold

Used to issue a warning if the condensation pump exceeds
the permissible number of cycles within a 24-hour period

Excessive

Moisture:
Condensation

Pump Running Time

Warning Threshold

Used to issue a warning if the condensation pump has run

longer than the permissible running time

Alarm Relay

Used to enable or disable the alarm relay

Audible Alarm

Used to enable or disable the audible alarm

Alarm Reset

Used to enable the alarm to be reset automatically (Auto)
or manually (Manual)

Trap Receiver

Used to activate trap receivers 1 through 4

Server Intake
Temperature Trap

Message Text

Used to enter information that displays when a server

intake temperature trap is received