HP Modular Cooling System User Manual
Page 42
Cooling performance parameter settings 42
Parameter
Function
Low Temperature
Threshold
Used to issue a warning if the low temperature threshold
temperature is exceeded
Water Flow Loss
Emergency Door
Opening
Temperature
Threshold
Used to open the HP Modular Cooling System doors when
the temperature threshold is exceeded and water loss is
detected.
This value cannot be lower than 5°C (41°F) above or more
than 20°C (68°F) above the Server Intake Temperature Set
Point.
High Temperature
Emergency Door
Opening Threshold
Used to open the MCS doors when the temperature
threshold is exceeded.
This value:
•
Cannot be lower than 5°C (41°F) above or more than
20°C (68°F) above the Server Intake Temperature Set
Point
•
Cannot be less than the Water Flow Loss Emergency
Door Opening Temperature Threshold
Excessive
Moisture:
Condensation
Pump Cycles
Warning Threshold
Used to issue a warning if the condensation pump exceeds
the permissible number of cycles within a 24-hour period
Excessive
Moisture:
Condensation
Pump Running Time
Warning Threshold
Used to issue a warning if the condensation pump has run
longer than the permissible running time
Alarm Relay
Used to enable or disable the alarm relay
Audible Alarm
Used to enable or disable the audible alarm
Alarm Reset
Used to enable the alarm to be reset automatically (Auto)
or manually (Manual)
Trap Receiver
Used to activate trap receivers 1 through 4
Server Intake
Temperature Trap
Message Text
Used to enter information that displays when a server
intake temperature trap is received