Web interface 13

Indicators

Meaning

Operator display alarm message Water Valve?

Web interface alarm message

Water Valve Failed

Condition

Water flow valve is closed, and water flow is detected.

Modules

Water group

SNMP notification

Warning

Type of message

Warning

Solution:

1.

Verify that the water valve is closed.

2.

Contact HP, or see the HP website (

http://www.hp.com

).

Leak detector sensor is not working properly

Indicators

Meaning

Operator display alarm message Leak detector?

Web interface alarm message

Leak detector Failed

Condition

Leak detector sensor is not working properly.

Sensors

Leak detector sensor

SNMP notification

Warning

Type of message

Warning

Solution:
Contact HP, or see the HP website (

http://www.hp.com

).

Uneven heat load

Indicators

Meaning

Operator display alarm message Heat Load?

Web interface alarm message

Heat Load Warning

Condition

Measured air temperature values are dramatically different from top to
bottom.

Sensors

Air temperature sensors

SNMP notification

Warning

Type of message

Warning

Solution:

1.

Verify that nothing is blocking the heat path.

2.

Verify that the servers are evenly installed over the height of the server rack and any open U-space is
closed with blanking panels.

3.

Adjust the Temperature Difference for Heat Load Warning in the Advanced tab.

Heat overload condition (High Temperature Threshold field)

Indicators

Meaning

Operator display alarm message Temperature too high