HP Modular Cooling System User Manual
Page 16
Web interface 16
Indicators
Meaning
Modules or sensors
Server Intake Temperature, Water Flow Meter
SNMP notification
Critical
Type of message
Alarm
Solution:
1.
Verify the water supply and that the MCS unit is receiving water.
2.
Verify that the water pressure delta is accurate.
3.
Verify that the water flow loss emergency door opening temperature threshold is not less than 5°C (9°F)
or more than 20°C (36°F) above the Server Intake Temperature Set Point.
4.
Adjust the temperature in the Server Intake Temperature Set Point or the Water Flow Loss Emergency
Door Opening Temperature Threshold fields to prevent false alarms.
IMPORTANT:
Use caution when entering temperatures in the Emergency Door Opening fields.
Setting the temperature thresholds too low might cause the MCS unit to shut down.
Emergency Door Opening due to High Temperature (35/36/38°C) (95/97/100°F)
Indicators
Meaning
Operator display alarm message Emergency Door, Heat
Web interface alarm message
Emergency Door Opening due to High Temperature (35/36/38°C)
(95/97/100°F)
The interface alarm message displays the temperatures of the fans so that
you can see which temperature has been exceeded and had caused the
alarm.
Condition
The High Temperature Emergency Door Opening Threshold has been
exceeded.
Modules or sensors
Server Intake Temperature
SNMP notification
Critical
Type of message
Alarm
Solution:
1.
Verify the water supply and that the MCS unit is receiving water.
2.
Verify that the High Temperature Emergency Door Opening Threshold is not less than 5°C (41°F) above
or more than 20°C (68°F) above the Server Intake Temperature Set Point, or that it is not below the
Water Flow Loss Emergency Door Opening Temperature Threshold.
3.
Adjust the temperature in the Server Intake Temperature Set Point or the Water Flow Loss Emergency
Door Opening Temperature Threshold fields to prevent false alarms.
IMPORTANT:
Use caution when entering temperatures in the Emergency Door Opening fields.
Setting the temperature thresholds too low might cause the MCS unit to shut down.
The condensation pump has exceeded x cycles
Indicators
Meaning
Operator display alarm message Excessive moisture
Web interface alarm message
The condensation pump has exceeded x cycles