Cooling performance parameter settings

Cooling performance parameter settings overview

The MCS unit has several cooling performance parameter settings. These settings control the fan speed and
water flow to meet the cooling needs of the rack-mounted components.
The temperature of the server intake air is controlled by varying the opening percentage of the water valve

inside the MCS unit. When the server intake air temperature is above the Server Intake Temperature Set

Point, the opening percentage of the water valve increases. When the server intake air temperature is below
the Server Intake Temperature Set Point, the opening percentage of the water valve decreases.
The level of speed for each fan unit is controlled through the control system using the server intake and server

exhaust temperatures.

Parameter

Function

Server Intake

Temperature Set
Point

Used to control the desired air temperature going into the

front of the servers

High Temperature

Threshold

Used to issue a Critical alarm if the high temperature

threshold temperature is exceeded

Warning
Temperature

Threshold

Used to issue a warning if the warning temperature

threshold temperature is exceeded