NORDAC AS-Interface Manual
66
BU
0090
GB
7.2 Error messages
Table of possible bus-specific error messages
Display
in the ControlBox
Group
Details in
P700 / P701
Fault
Text in the ParameterBox
Cause
• Remedy
10.0 Telegram
downtime
Data transfer is faulty. Check P513.
• Check external Bus connection.
• Check bus protocol program process.
• Check Bus Master.
10.2
External bus module
telegram timeout
Telegram transfer is faulty.
• Check external connection.
• Check bus protocol program process.
• Check Bus Master.
10.4
External bus module
initialisation failure
• Check
P746.
• Bus module not correctly plugged in.
• Check Bus module current supply.
10.1
10.3
10.5
10.6
10.7
External Bus module system
failure
Further details can be found in Section 4.2.
E010
10.8 External
module
communication failure
Connection fault / error in the external component
- B1000 (820 pages)
- B2000 (60 pages)
- B1050 (36 pages)
- B2050 (48 pages)
- B1091 (28 pages)
- B1091-1 (28 pages)
- B1092 (52 pages)
- B1901 (6 pages)
- B1904 (23 pages)
- BU0180 (184 pages)
- BU0200 (314 pages)
- BU0210 (60 pages)
- BU0220 (100 pages)
- BU0230 (76 pages)
- BU0240 (40 pages)
- BU0260 (116 pages)
- BU0270 (76 pages)
- BU0280 (78 pages)
- BU0290 (76 pages)
- BU0300 (148 pages)
- BU0310 (8 pages)
- BU0320 (2 pages)
- BU0500 (180 pages)
- BU0505 (188 pages)
- BU0510 (81 pages)
- BU0530 (56 pages)
- BU0540 (64 pages)
- BU0550 (100 pages)
- BU0560 (4 pages)
- BU0570 (44 pages)
- BU0590 (48 pages)
- BU0700 (131 pages)
- BU0701 (1 page)
- BU0710 (32 pages)
- BU0750 (157 pages)
- BU0930 (8 pages)
- BU0940 (44 pages)
- BU2100 (34 pages)
- BU2200 (42 pages)
- MI0300 (36 pages)
- MI0700 (84 pages)
- BU0000 (85 pages)
- BU0010 (4 pages)
- BU0020 (104 pages)
- BU0040 (60 pages)