5 Data transfer / Parameter-string transfer

BU 0090 GB

43

5.1 Read ID string

(read from slave)

Via the AS interface module, specific data from the frequency inverter can be read out by means of the Read
ID string

command. The information and values in the ID string will first be shown when the AS interface has

recognised the frequency inverter.

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

03

hex

2D

hex

07

hex

12

hex

12

hex

03

hex

FF

hex

03

hex

03

hex

03

hex

18 19 20 21 22 23

03

hex

01

hex

Byte

Contents

0-6, 8/11/14/20/23: determined according to the AS interface specification (4I/4O-operation; supports diagnosis; protocol)
7

:

version of AS interface module (with 1 decimal place)

9/10 :

frequency inverter version (P707[0])

12/13 :

frequency inverter revision (P707[1])

15/16 :

frequency inverter power (P743)

17

:

frequency inverter voltage range (P747);

03

hex

= 100 V to 120 V

13

hex

= 200 V to 240 V

23

hex

= 380 V to 480 V

93

hex

= P747 not available

18/19 :

frequency inverter configuration (P743)

21/22 :

frequency inverter ID (for servicing)

In word variables, the high-byte is transferred before the low-byte. For details and information regarding the particular
parameters, please refer to the operating instructions of the frequency inverter used.

5.2 Read diagnosis string

(read from slave)

By means of the Read diagnosis string command, the process and status data of the frequency inverter can be
read out and analysed via the AS interface. The information and values in the diagnosis string will first be
shown when the AS interface has recognised the frequency inverter.

0 1 2 3 4 5 6 7 8 9 10 11 12 13

Status

00

hex

BusIO

In

BusIO

Out

Error

No.

ZSW IW1 IW2 IW3

Byte Contents

0

:

Module status or status of the AS interface module (see Section 4.2)

1 :

Reserved

2

:

Status of AS interface inputs (BusIO In Bits)

3

:

Status of AS interface outputs (BusIO Out Bits)

4/5

:

Inverter error (P700)

6/7

:

PZD-ZSW

(Status word, see Section 5.4.1)

8/9

:

PZD-IW1 (actual

value 1, see Section 5.4.2)

10/11

:

PZD-IW2 (actual

value 2, see Section 5.4.3)

12/13

:

PZD-IW3 (actual

value 3, see Section 5.4.3)

In word variables, the high-byte is transferred before the low-byte. For details and information regarding the particular
parameters, please refer to the operating instructions of the frequency inverter used.