1 read id string, 2 read diagnosis string – NORD Drivesystems BU0090 User Manual
Page 43
![background image](/manuals/372808/43/background.png)
5 Data transfer / Parameter-string transfer
BU 0090 GB
43
5.1 Read ID string
(read from slave)
Via the AS interface module, specific data from the frequency inverter can be read out by means of the Read
ID string
command. The information and values in the ID string will first be shown when the AS interface has
recognised the frequency inverter.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
03
hex
2D
hex
07
hex
12
hex
12
hex
03
hex
FF
hex
03
hex
03
hex
03
hex
18 19 20 21 22 23
03
hex
01
hex
Byte
Contents
0-6, 8/11/14/20/23: determined according to the AS interface specification (4I/4O-operation; supports diagnosis; protocol)
7
:
version of AS interface module (with 1 decimal place)
9/10 :
frequency inverter version (P707[0])
12/13 :
frequency inverter revision (P707[1])
15/16 :
frequency inverter power (P743)
17
:
frequency inverter voltage range (P747);
03
hex
= 100 V to 120 V
13
hex
= 200 V to 240 V
23
hex
= 380 V to 480 V
93
hex
= P747 not available
18/19 :
frequency inverter configuration (P743)
21/22 :
frequency inverter ID (for servicing)
In word variables, the high-byte is transferred before the low-byte. For details and information regarding the particular
parameters, please refer to the operating instructions of the frequency inverter used.
5.2 Read diagnosis string
(read from slave)
By means of the Read diagnosis string command, the process and status data of the frequency inverter can be
read out and analysed via the AS interface. The information and values in the diagnosis string will first be
shown when the AS interface has recognised the frequency inverter.
0 1 2 3 4 5 6 7 8 9 10 11 12 13
Status
00
hex
BusIO
In
BusIO
Out
Error
No.
ZSW IW1 IW2 IW3
Byte Contents
0
:
Module status or status of the AS interface module (see Section 4.2)
1 :
Reserved
2
:
Status of AS interface inputs (BusIO In Bits)
3
:
Status of AS interface outputs (BusIO Out Bits)
4/5
:
Inverter error (P700)
6/7
:
PZD-ZSW
(Status word, see Section 5.4.1)
8/9
:
PZD-IW1 (actual
value 1, see Section 5.4.2)
10/11
:
PZD-IW2 (actual
value 2, see Section 5.4.3)
12/13
:
PZD-IW3 (actual
value 3, see Section 5.4.3)
In word variables, the high-byte is transferred before the low-byte. For details and information regarding the particular
parameters, please refer to the operating instructions of the frequency inverter used.