NORD Drivesystems BU0090 User Manual
Page 36
NORDAC AS-Interface Manual
36
BU
0090
GB
Parameter
Setting value / Description / Note
Comments
P546 (P)
Bus setpoint 1
In this parameter, a function is assigned to the delivered setpoint 1 (SW1) for bus control.
NOTE:
Further details can be found in the respective FI manual or in the description of P400.
0 ... 7 (47)
[ 1 ]
SK 300E, SK 700E SK 750E
0 =
Off
1 =
Setpoint frequency (16 bit)
2 =
16 Bit setpoint position (only posicon,
SK700/750E
)
3 =
32 Bit setpoint position (only posicon,
SK700/750E
and if PPO- type 2 or 4 are
selected)
4 =
Control terminals posicon (only posicon,
SK700/750E
, 16Bit)
5 =
Setpoint position (16 Bit) increment
1
(onlyposicon, SK700/750E)
6 =
Setpoint position (32 Bit) increment
1
(onlyposicon, SK700/750E)
7 =
Bus IO In Bits 0-7
SK 500E
0 =
Off
1 =
Setpoint frequency (16 bit)
2 =
Torque current limit (P112)
3 =
Actual frequency PID
4 =
Frequency addition
5 =
Frequency subtraction
6 =
Current limit (P536)
7 =
Maximum frequency (P105)
8 =
Actual PID frequency limited
9 =
Actual PID frequency monitored
10 =
Torque servo mode (P300)
11 =
Lead torque (P214)
12 =
Reserved
13 =
Multiplication
14 =
PI process controller actual value
15 =
PI process controller setpoint
16 =
PI process controller lead
17 =
Digital In bits 0...7
18 =
Reserved
19 =
Set relay (P434/441/450/455=38)
20 =
Set analog output (P418=31)
21 =
... 45 reserved
46 =
Setpoint torque process controller
47 =
Gearing transfer factor
P547 (P)
Bus setpoint 2
In this parameter, a function is assigned to the delivered setpoint 2 (SW2) for bus control.
0 ... 46 (47)
[ 0 ]
0 =
Off
1 =
Setpoint frequency
2 =
Torque current limit (P112)
3 =
Actual frequency PID
4 =
Frequency addition
5 =
Frequency subtraction
6 =
Current limit (not SK 300E)
7 =
Maximum frequency (not SK 300E)
8 =
Actual PID frequency limited
9 =
Actual PID frequency monitored
10 =
Torque (not SK 300E)
11 =
Torque lead (not SK 300E)
12 =
Control terminals posicon (not SK 300E)
13 =
Multiplication (not SK 300E)
14 =
PI process controller actual value
15 =
PI process controller setpoint
16 =
PI process controller lead
17 =
Digital In bits 0...7
18 =
Curve travel calculator (not SK 300E)
19 =
Set relay
20 =
Set analog output
21 =
... 45 Reserved
46 =
Setpoint, torque process controller
(not SK 300E)
47 =
Gearing transfer factor (only SK 500E)
P548 (P)
Bus setpoint 3
In this parameter, a function is assigned to the delivered setpoint 3 (SW3) for bus control. This is
only available if P546
≠
3 (only applies for SK 700E / SK 750E).
0 ... 46 (47)
[ 0 ]
For setting values, see parameter (P547)