NORDAC AS-Interface Manual
56
BU
0090
GB
For this, the following FI parameters must be set as follows:
P480 [01] Bus IO In Bit 0
1 = Enable right
P480 [02] Bus IO In Bit 1
2 = Enable left
P480 [03] Bus IO In Bit 2
8 = Parameter switch-over
P480 [04] Bus IO In Bit 3
12 = Error acknowledgement
P481 [01] Bus IO Out Bit 0
2 = Inverter operating
P481 [02] Bus IO Out Bit 1
7 = Error
P509 interface
0 = Control terminals or keyboard control
P543 Bus actual value 1
12 = Bus IO Out Bits 0-7
P546 Bus setpoint 1
17 = Bus IO In Bits 0-7
For the switch-over of the parameter set it should be noted that the parameters dependent on the parameter
set, e.g. P543 and P546 are also accordingly parameterised onto Bus IO Bits.
6.1.3
AS interface binary values (Digital inputs and outputs)
The following example purely serves for the I/O expansion of the control signals and can also be operated
without the AS interface master.
For example, a frequency inverter is to be enabled for the directions of rotation right and left via the digital AS
interface In Bits (Sensor Dig), and the direction of rotation changed via the second sensor input. In addition, a
setpoint increase is to be made via fixed frequency 1. An error acknowledgement is to be performed with the
fourth and last In Bit (Sensor Dig). The operation and the error indication of the frequency inverter are to be
output via the first two of the four digital AS interface Out Bits (Actuator Dig).
For this, the following FI parameters must be set as follows:
P429 Fixed frequency 1
e.g. 10 Hz
P480 [05] Bus IO In Bit 4 (Sensor Dig In 1)
1 = Enable right
P480 [06] Bus IO In Bit 5 (Sensor Dig In 2)
3 = Reverse direction of rotation
P480 [07] Bus IO In Bit 6 (Sensor Dig In 3)
4 = Fixed frequency 1
P480 [08] Bus IO In Bit 7 (Sensor Dig In 4)
12 = Error acknowledgement
P481 [05] Bus IO Out Bit 4 (Actuator Dig Out 1)
2 = Inverter operating
P481 [06] Bus IO Out Bit 5 (Actuator Dig Out 2)
7 = Error
P509 interface
0 = Control terminals or keyboard control
P543 Bus actual value 1
12 = Bus IO Out Bits 0-7
P546 Bus setpoint 1
17 = Bus IO In Bits 0-7