5 Data transfer / Parameter-string transfer
BU 0090 GB
49
5.4.3
Actual value 2 and actual value 3 (IW2/3)
It is possible to forward two more actual values to the controller if PPO type 2 or 4 is used for transfer.
The actual value 2 (IW2) is transmitted in PZD4. The value to be transferred can be selected in P544 (actual
bus value 2). Actual value 3 (IW3) can be transmitted in PDZ3 if actual value 1 is not a 32 Bit value. The value
to be transferred can be selected in P545 (actual bus value 3). The standardisation corresponds to actual
value 1 (see above)
5.4.4
The status machine
The frequency inverter passes through a status machine. The changes between various states are triggered
by the respective control commands in the process data control word. The actual status is returned in the
process data status word.
After switching on, the inverter is in switch-on disabled status. This status can only be ended by transmitting
the “Shut down (Off 1)” command.
The answer to a Master telegram normally does not yet contain a reaction to the control command. The
controller has to check the answers from the slaves as to whether the control command has been carried out.
The following Bits indicate the status of the frequency inverter:
Status
Bit 6
Switch-on
disable
Bit 5
Emergency
stop
Bit 4
Disable
voltage
Bit 3
Fault
Bit 2
Operation
enabled
Bit 1
Standby
Bit 0
Ready for
switch-on
Not ready to start
0
X
X
0
0
0
0
Starting
disabled 1 X X 0 0 0 0
Ready
to
start 0 1 1 0 0 0 1
Activated
0 1 1 0 0 1 1
Operation
enabled 0 1 1 0 1 1 1
Fault
0 X X 1 0 0 0
Error
active 0 X X 1 1 1 1
Emergency
stop
active
0 0 1 0 1 1 1