beautypg.com

NORD Drivesystems BU0090 User Manual

Page 60

background image

NORDAC AS-Interface Manual

60

BU

0090

GB

Example of reading direct parameters:
In order to check whether the direct parameter has been correctly transferred, a plausibility check should be
performed. For this, the corresponding index must be sent with the function Write Parameter. For the start-up
time P102 in parameter set 1, this would be the Index 0054

hex

. Only the Index needs to be transferred, i.e. the

number of parameter Bytes is 2.
In order to read out the parameter value P102, proceed as follows:

• Transfer the Index with Write Parameter
• Then read out the parameter value with Read Parameter

After the successful completion of the Write order, start the Read order with command number 41.


The Index and the parameter value are then output to the reception buffer.

Data Byte
in DB13

Value in
hex

Meaning / Note

DBB228

04

Number of parameter bytes, 0A4

hex

corresponds to 04

dec

DBB229 00

Index:

DBB230

54

Index: start-up time P102, parameter set 1

DBB231

03

Parameter value: takes the resolution 0.01 into account

DBB232

E8

Parameter value: takes the resolution 0.01 into account


If subsequently, i.e. without a further Write order being started in the meantime, one or more Read orders are
started consecutively, the AS interface reads the corresponding parameter values consecutively according to
the Index sequence of the direct parameter table. The AS interface automatically counts up the index.

Note:

This automatic Index increase only applies to the direct parameter function.

As a result, after the next Read Parameter String order, the parameter value P102, start-up time, is read out
from parameter set 2 in the reception buffer.

Data Byte
in DB13

Value in
hex

Meaning / Note

DBB228

04

Number of parameter bytes, 0A4

hex

corresponds to 04

dec

DBB229 00

Index:

DBB230

55

Index: start-up time P102, parameter set 2

DBB231

07

parameter value, taking the resolution 0.01 into account

DBB232

D0

parameter value, taking the resolution 0.01 into account

Data Byte
in DB13

Value in
hex

Meaning / Note

DBB4

40

Write the command number for the parameter string

DBB5 01

Slave

address

DBB6

02

Number of parameter Bytes, 02

hex

DBB7

00

Byte 0: Index

DBB8

54

Byte 1: Index, start-up time P102, parameter set 1

Data Byte
in DB13

Value in
hex

Meaning / Note

DBB4

41

Read the command number for the parameter string

DBB5 01

Slave

address