4.1.2
Additional parameters
Parameter
Setting value / Description / Note
Comments
P509
Interface
SK 300E, SK 700E, SK 750E
0 ... 21
[ 0 ]
Selection of the interface from which the inverter is controlled.
0 = Control terminal or keyboard control
with the Control Box (option), the ParameterBox
(option) or the Potentiometer option
1 = Control terminals only,
the inverter can only be controlled via the 4 digital inputs and the
analog input.
… other setting possibilities (bus control),
see the manual for the frequency inverter
P509
Control word source
SK 500E
0 ... 10
[ 0 ]
Selection of the interface via which the FI is controlled.
0 = Control terminal or keyboard control with the Control Box (if P510=0), the
ParameterBox (not extension parameter box) or via BUS I/O Bits.
1 = Only control terminals , the FI can only be controlled via the digital and analog inputs or
via the bus I/O Bits.
2 = USS
, the control signals (enable, rotation direction, etc.) are transferred via the RS485
interface, the setpoint via the analog input or the fixed frequencies.
3 = CAN control word
4 = Profibus control word
5 = InterBus control word
6 = CANopen control word
7 = DeviceNet control word
8 = Reserved
9 = CAN
Broadcast
10 = CANopen Broadcast
P510
Auxiliary setpoint interface
SK 300E, SK 700E, SK 750E
Selection of the interface from which the inverter is controlled.
0 ... 8
[ 0 ]
0 = Auto:
The auxiliary setpoint value is automatically
taken from the interface of the main setpoint value
P509 >interface<
1 = USS
2 = CANbus
3 = Profibus
4 = InterBus
5 = CANopen
6 = DeviceNet
7 =
Reserved
8 = CAN Broadcast
Note:
For control via the AS interface this parameter
must be set for a value for control via control
terminals. Otherwise only the safety function is
active via the AS interface (see note at the end of
this section).
Note:
For control via the AS interface this parameter
must be set for a value for control via control
terminals. Otherwise only the safety function is
active via the AS interface (see note at the end of
this section).